Schneider Electric GV4PB02S Motbreakgv4Pbul489Th/Mag 2A 100Ka Elink

(No reviews yet) Write a Review
SKU:
GV4PB02S
UPC:
3.60649E+12
Condition:
New
Standards:
EN/IEC 60947-1 || EN/IEC 60947-2 || EN/IEC 60947-4-1 || UL 489 || CSA C22.2 No 5
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-2 || 600Y/347 V AC 60 Hz UL 489
[Ui] Rated Insulation Voltage:
800 V AC 50/60 Hz IEC 60947-2
Ambient Air Temperature For Operation:
-25-70 °C
Fire Resistance:
960 °C IEC 60695-2-11
Device Short Name:
GV4PB
Ik Degree Of Protection:
IK07 IEC 62262
Halogen Content Performance:
Halogen free plastic parts product
Product Certifications:
IEC || UL || CSA
Product Or Component Type:
motor circuit breaker
Control Type:
toggle
Power Dissipation Per Pole:
4.6 W
Range Of Product:
TeSys GV4
Ambient Air Temperature For Storage:
-50-85 °C
Maximum Operating Rate:
25 cyc/h
Height:
171 mm
Connections - Terminals:
EverLink BTR screw connectors top) 1 1.5-70 mm² - rigid || EverLink BTR screw connectors top) 1 1.5-50 mm² - flexible || EverLink BTR screw connectors bottom) 1 2.5-95 mm² - rigid || EverLink BTR screw connectors bottom) 1 2.5-70 mm² - flexible
Utilisation Category:
category A IEC 60947-2 || AC-3 IEC 60947-4-1
Mechanical Durability:
40000 cycles
Suitability For Isolation:
yes IEC 60947-1
Trip Unit Technology:
thermal-magnetic || electronic
Operating Altitude:
5000 m
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Sustainable Offer Status:
Green Premium product
Electrical Durability:
40000 cycles AC-3 440 V In/2 || 40000 cycles AC-3 440 V In
Magnetic Tripping Current:
34-34 A
Net Weight:
1.45 kg
Eu Rohs Directive:
Compliant with Exemptions
Device Application:
motor protection
Tightening Torque:
9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
Mercury Free:
Yes
Width:
81 mm
Range:
TeSys Deca
Phase Failure Sensitivity:
yes IEC 60947-4-1
Color:
Gray RAL 7016)
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Product Name:
TeSys GV4 || TeSys Deca
Warranty:
18 months
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Environmental Disclosure:
ENVPEP1704004EN
Line Rated Current:
0.0833333333333333
Circularity Profile:
ENVEOLI1704004EN
[Ith] Conventional Free Air Thermal Current:
115 A IEC 60947-4-1
Rated Duty:
continuous IEC 60947-4-1
Depth:
116 mm
Mechanical Robustness:
vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Pollution Degree:
3
Climatic Withstand:
IACS E10
Poles Description:
3P
Pvc Free:
Yes
Rohs Exemption Information:
Yes
Operating Position:
any position
Ip Degree Of Protection:
IP40 IEC 60529
Breaking Capacity:
100 kA SCCR 240 V AC 60 Hz UL 489 || 65 kA SCCR 480Y/277 V AC 60 Hz UL 489 || 25 kA SCCR 600Y/347 V AC 60 Hz UL 489 || 120 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 || 70 kA Icu 440 V AC 50/60 Hz IEC 609
[Ics] Rated Service Short-Circuit Breaking Capacity:
100 % 220/240 V AC 50/60 Hz IEC 60947-2 || 100 % 380/415 V AC 50/60 Hz IEC 60947-2 || 100 % 440 V AC 50/60 Hz IEC 60947-2 || 100 % 500 V AC 50/60 Hz IEC 60947-2 || 100 % 525 V AC 50/60 Hz IEC 60947-2 || 25 % 660/690 V AC 50/60 Hz IEC 60947-2
Datasheet:
View
  • Schneider Electric GV4PB02S Motbreakgv4Pbul489Th/Mag 2A 100Ka Elink
  • Schneider Electric GV4PB02S Motbreakgv4Pbul489Th/Mag 2A 100Ka Elink
$508.00

Description

TeSys GV motor circuit breaker, 3 poles (3P), 2A/690V, for protection of 3-phase motors 0.25-0.75kW@400V. Multifunction circuit breaker UL489 compliant, it provides thermal magnetic protection and advanced motor protection, breaking capacity Icu 100kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 0.8-2A, a selectable tripping class 10 or 20, rated tripping current 125%, magnetic protection at 17 In. Advanced protections are adjustable with a smartphone using wireless NFC and include short time delay protection Isd with a setting range 5-13 Ir, phase unbalance and loss protection, ground fault protection, locked rotor (jam), long start. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). It can be equiped externally with 1 or 2 auxiliary SDx modules in order to have alarming and fault differentiation. Multi standards certified (IEC, UL 489, CSA C22.2 N°5), Green Premium compliant (RoHS/REACh).
View AllClose