- Mounting Mode:
- I-Line bracket)
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Quantity Per Set:
- 1
- Warranty:
- 18 months
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Continuous Current Rating:
- 0.8
- Ambient Air Temperature For Operation:
- -2-70 °C
- Communication Interface:
- Modbus || Ethernet
- Wire Stripping Length:
- 16 mm
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Circularity Profile:
- ENVEOLI2206027EN
- Height:
- 163 mm
- Protected Poles Description:
- 2t
- Trip Unit Technology:
- thermal-magnetic
- Sustainable Offer Status:
- Green Premium product
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Utilisation Category:
- category A
- Net Weight:
- 2.2 kg
- Rohs Exemption Information:
- Yes
- Pvc Free:
- Yes
- Width:
- 104 mm
- Color:
- Black
- Suitability For Isolation:
- yes IEC 60947-2
- Terminal Identifier:
- AL150HD
- Control Type:
- toggle
- Mercury Free:
- Yes
- Magnetic Tripping Current:
- 750-750 A
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Mounting Support:
- bracket
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Eu Rohs Directive:
- Compliant with Exemptions
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Pollution Degree:
- 3 IEC 60947-1
- Quality Labels:
- CE
- Ambient Air Temperature For Storage:
- -50-85 °C
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Mounting Height:
- 3 in
- Circuit Breaker Application:
- HACR rated
- Phase Connection:
- AB
- Environmental Disclosure:
- ENVPEP2206027EN
- Device Application:
- distribution
- Line Rated Current:
- 15-15 A
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Product Certifications:
- UL || CSA || NOM
- Electrical Connection:
- I-Line connection, line || lugs, load
- Network Frequency:
- 50/60 Hz
- Product Name:
- PowerPact H
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Depth:
- 86 mm
- Magnetic Hold Current:
- 350 A
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Breaking Capacity Code:
- D
- Poles Description:
- 2P
- Range:
- PowerPact
- QN-QUOTE-REQUEST:
- true