1
Magnetic Hold Current:
400 A
Communication Interface:
Modbus || Ethernet
Ambient Air Temperature For Operation:
-2-70 °C
Range:
PowerPact
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Breaking Capacity:
25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
Electrical Connection:
I-Line connection, line || lugs, load
Mercury Free:
Yes
Depth:
86 mm
Ip Degree Of Protection:
front cover IP40 IEC 60529
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Breaking Capacity Code:
D
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Magnetic Tripping Current:
850-850 A
Rohs Exemption Information:
Yes
Protected Poles Description:
2t
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Quality Labels:
CE
Poles Description:
2P
Pvc Free:
Yes
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Device Application:
distribution
Pollution Degree:
3 IEC 60947-1
Net Weight:
2.2 kg
Mounting Mode:
I-Line bracket)
Control Type:
toggle
Wire Stripping Length:
16 mm
Circularity Profile:
ENVEOLI2206027EN
Local Signalling:
switched off (OFF) 1 trip indicator green)
Product Certifications:
UL || CSA || NOM
[Ics] Rated Service Breaking Capacity:
25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Product Or Component Type:
circuit breaker
Color:
Black
Network Frequency:
50/60 Hz
Environmental Disclosure:
ENVPEP2206027EN
Mounting Height:
3 in
Product Name:
PowerPact H
Terminal Identifier:
AL150HD
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Circuit Breaker Application:
HACR rated
Eu Rohs Directive:
Compliant with Exemptions
Trip Unit Technology:
thermal-magnetic
Warranty:
18 months
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Sustainable Offer Status:
Green Premium product
Phase Connection:
CA
Width:
104 mm
Suitability For Isolation:
yes IEC 60947-2
Height:
163 mm
Mounting Support:
bracket
Continuous Current Rating:
0.8
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Line Rated Current:
40-40 A
Ambient Air Temperature For Storage:
-50-85 °C
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Utilisation Category:
category A
Brochure:
View
Catalog:
View
Datasheet:
View
  • Schneider Electric HDA260405 Molded Case Circuit Breaker 600V 40A
  • Schneider Electric HDA260405 Molded Case Circuit Breaker 600V 40A
$1,348.50

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 40A, 2 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with a CA phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose