Schneider Electric HDA260501 Molded Case Circuit Breaker 600V 50A

(No reviews yet) Write a Review
SKU:
HDA260501
UPC:
7.85901E+11
Condition:
New
Quantity Per Set:
1
[Ics] Rated Service Breaking Capacity:
25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Mounting Mode:
I-Line bracket)
Ambient Air Temperature For Storage:
-50-85 °C
Circularity Profile:
ENVEOLI2206027EN
Breaking Capacity Code:
D
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Quality Labels:
CE
Phase Connection:
AB
Circuit Breaker Application:
HACR rated
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Ip Degree Of Protection:
front cover IP40 IEC 60529
Trip Unit Technology:
thermal-magnetic
Continuous Current Rating:
0.8
Terminal Identifier:
AL150HD
Sustainable Offer Status:
Green Premium product
Communication Interface:
Modbus || Ethernet
Warranty:
18 months
Magnetic Tripping Current:
850-850 A
Rohs Exemption Information:
Yes
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Wire Stripping Length:
16 mm
Breaking Capacity:
25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
Product Or Component Type:
circuit breaker
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Device Application:
distribution
Environmental Disclosure:
ENVPEP2206027EN
Net Weight:
2.2 kg
Product Certifications:
UL || CSA || NOM
Width:
104 mm
Ambient Air Temperature For Operation:
-2-70 °C
Eu Rohs Directive:
Compliant with Exemptions
Control Type:
toggle
Mounting Support:
bracket
Pollution Degree:
3 IEC 60947-1
Mounting Height:
3 in
Color:
Black
Magnetic Hold Current:
400 A
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Poles Description:
2P
Mercury Free:
Yes
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Electrical Connection:
I-Line connection, line || lugs, load
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Utilisation Category:
category A
Line Rated Current:
50-50 A
Network Frequency:
50/60 Hz
Height:
163 mm
Local Signalling:
switched off (OFF) 1 trip indicator green)
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Pvc Free:
Yes
Depth:
86 mm
Protected Poles Description:
2t
Range:
PowerPact
Suitability For Isolation:
yes IEC 60947-2
Product Name:
PowerPact H
Brochure:
View
Catalog:
View
Datasheet:
View
  • Schneider Electric HDA260501 Molded Case Circuit Breaker 600V 50A
  • Schneider Electric HDA260501 Molded Case Circuit Breaker 600V 50A
$899.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 50A, 2 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an AB phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.