- Mounting Height:
- 3 in
- Network Frequency:
- 50/60 Hz
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Quality Labels:
- CE
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Rohs Exemption Information:
- Yes
- Control Type:
- toggle
- Communication Interface:
- Modbus || Ethernet
- Quantity Per Set:
- 1
- Utilisation Category:
- category A
- Depth:
- 86 mm
- Electrical Connection:
- I-Line connection, line || lugs, load
- Phase Connection:
- BC
- Circuit Breaker Application:
- HACR rated
- Sustainable Offer Status:
- Green Premium product
- Protected Poles Description:
- 2t
- Net Weight:
- 2.2 kg
- Product Name:
- PowerPact H
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Ambient Air Temperature For Storage:
- -50-85 °C
- Environmental Disclosure:
- ENVPEP2206027EN
- Pvc Free:
- Yes
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Width:
- 104 mm
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Mounting Mode:
- I-Line bracket)
- Eu Rohs Directive:
- Compliant with Exemptions
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Warranty:
- 18 months
- Circularity Profile:
- ENVEOLI2206027EN
- Product Or Component Type:
- circuit breaker
- Mercury Free:
- Yes
- Ambient Air Temperature For Operation:
- -2-70 °C
- Product Certifications:
- UL || CSA || NOM
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Continuous Current Rating:
- 0.8
- Range:
- PowerPact
- Color:
- Black
- Suitability For Isolation:
- yes IEC 60947-2
- Line Rated Current:
- 50-50 A
- Pollution Degree:
- 3 IEC 60947-1
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Terminal Identifier:
- AL150HD
- Device Application:
- distribution
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Height:
- 163 mm
- Wire Stripping Length:
- 16 mm
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Mounting Support:
- bracket
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Trip Unit Technology:
- thermal-magnetic
- Magnetic Hold Current:
- 400 A
- Breaking Capacity Code:
- D
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Poles Description:
- 2P
- Magnetic Tripping Current:
- 850-850 A