- Terminal Identifier:
- AL150HD
- Magnetic Hold Current:
- 900 A
- Eu Rohs Directive:
- Compliant with Exemptions
- Quality Labels:
- CE
- Phase Connection:
- BC
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Height:
- 163 mm
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Sustainable Offer Status:
- Green Premium product
- Poles Description:
- 2P
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Mercury Free:
- Yes
- Product Name:
- PowerPact H
- Magnetic Tripping Current:
- 1700-1700 A
- Environmental Disclosure:
- ENVPEP2206027EN
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Color:
- Black
- Quantity Per Set:
- 1
- Utilisation Category:
- category A
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Ambient Air Temperature For Operation:
- -2-70 °C
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Wire Stripping Length:
- 16 mm
- Net Weight:
- 2.2 kg
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Device Application:
- distribution
- Warranty:
- 18 months
- Electrical Connection:
- I-Line connection, line || lugs, load
- Protected Poles Description:
- 2t
- Circuit Breaker Application:
- HACR rated
- Continuous Current Rating:
- 0.8
- Breaking Capacity Code:
- D
- Mounting Height:
- 3 in
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Product Certifications:
- UL || CSA || NOM
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Width:
- 104 mm
- Line Rated Current:
- 100-100 A
- Pvc Free:
- Yes
- Control Type:
- toggle
- Range:
- PowerPact
- Suitability For Isolation:
- yes IEC 60947-2
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Depth:
- 86 mm
- Trip Unit Technology:
- thermal-magnetic
- Mounting Support:
- bracket
- Communication Interface:
- Modbus || Ethernet
- Product Or Component Type:
- circuit breaker
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Pollution Degree:
- 3 IEC 60947-1
- Circularity Profile:
- ENVEOLI2206027EN
- Ambient Air Temperature For Storage:
- -50-85 °C
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Rohs Exemption Information:
- Yes
- Mounting Mode:
- I-Line bracket)
- QN-QUOTE-REQUEST:
- true