Schneider Electric

Schneider Electric HDF36125UK Molded Case Circuit Breaker 600V 125A

(No reviews yet) Write a Review
SKU:
HDF36125UK
UPC:
3606486282410
Condition:
New
Breaking Capacity Code:
D
Pollution Degree:
3 IEC 60947-1
Range:
PowerPact
Ip Degree Of Protection:
front cover IP40 IEC 60529
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Line Rated Current:
125-125 A
Mounting Mode:
unit mount busbar)
Mercury Free:
Yes
Width:
104 mm
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Ambient Air Temperature For Storage:
-50-85 °C
Quality Labels:
CE
Color:
Black
Warranty:
18 months
Pvc Free:
Yes
Protected Poles Description:
3t
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Eu Rohs Directive:
Compliant with Exemptions
Suitability For Isolation:
yes IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Network Frequency:
50/60 Hz
Mounting Support:
busbar
Accessory / Separate Part Type:
voltage release 24 V AC compartment
Trip Unit Technology:
thermal-magnetic
Utilisation Category:
category A
Poles Description:
3P
Circularity Profile:
ENVEOLI2206027EN
Breaking Capacity:
25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
Terminal Identifier:
AL150HD
Depth:
86 mm
Product Name:
PowerPact H
Communication Interface:
Modbus || Ethernet
Continuous Current Rating:
0.8
Height:
163 mm
Magnetic Tripping Current:
1700-1700 A
Sustainable Offer Status:
Green Premium product
Local Signalling:
switched off (OFF) 1 trip indicator green)
Control Type:
toggle
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Rohs Exemption Information:
Yes
Product Or Component Type:
circuit breaker
Product Certifications:
UL || CSA || NOM
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Circuit Breaker Application:
HACR rated
Environmental Disclosure:
ENVPEP2206027EN
Net Weight:
2.2 kg
Quantity Per Set:
1
Electrical Connection:
busbar connection, line || busbar connection, load
Wire Stripping Length:
16 mm
Device Application:
distribution
[Ics] Rated Service Breaking Capacity:
25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Ambient Air Temperature For Operation:
-2-70 °C
Magnetic Hold Current:
900 A
Brochure:
View
Catalog:
View
Datasheet:
View
$3,317.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has a busbar connection. This PowerPacT H, 125A, 3 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80%. This unit includes a factory installed 24VAC undervoltage trip. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose