- Device Application:
- distribution
- Depth:
- 86 mm
- Range:
- PowerPact
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Sustainable Offer Status:
- Green Premium product
- Product Name:
- PowerPact H
- Network Frequency:
- 50/60 Hz
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Net Weight:
- 2.2 kg
- Ambient Air Temperature For Operation:
- -2-70 °C
- Ambient Air Temperature For Storage:
- -50-85 °C
- Communication Interface:
- Modbus || Ethernet
- Terminal Identifier:
- AL150HD
- Control Type:
- toggle
- Height:
- 163 mm
- Environmental Disclosure:
- ENVPEP1311006EN
- Magnetic Tripping Current:
- 750-750 A
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Width:
- 104 mm
- Breaking Capacity Code:
- D
- Eu Rohs Directive:
- Compliant
- Quality Labels:
- CE
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Magnetic Hold Current:
- 350 A
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Pollution Degree:
- 3 IEC 60947-1
- Color:
- Black
- Poles Description:
- 2P
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Pvc Free:
- Yes
- Suitability For Isolation:
- yes IEC 60947-2
- Wire Stripping Length:
- 16 mm
- Mercury Free:
- Yes
- Product Or Component Type:
- circuit breaker
- Line Rated Current:
- 20-20 A
- Circuit Breaker Application:
- HACR rated
- Circularity Profile:
- ENVEOLI1311006EN
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Quantity Per Set:
- 1
- Utilisation Category:
- category A
- Rohs Exemption Information:
- Yes
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Continuous Current Rating:
- 1
- Warranty:
- 18 months
- Mounting Support:
- lug
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Trip Unit Technology:
- thermal-magnetic
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Protected Poles Description:
- 2t
- Mounting Mode:
- unit mount lug)
- Electrical Connection:
- lugs, line || lugs, load
- QN-QUOTE-REQUEST:
- true