- Utilisation Category:
- category A
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Net Weight:
- 2.2 kg
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Width:
- 104 mm
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Height:
- 163 mm
- Device Application:
- distribution
- Warranty:
- 18 months
- Breaking Capacity Code:
- D
- Protected Poles Description:
- 2t
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Mounting Mode:
- unit mount lug)
- Quantity Per Set:
- 1
- Poles Description:
- 2P
- Ambient Air Temperature For Operation:
- -2-70 °C
- Depth:
- 86 mm
- Suitability For Isolation:
- yes IEC 60947-2
- Product Name:
- PowerPact H
- Ambient Air Temperature For Storage:
- -50-85 °C
- Sustainable Offer Status:
- Green Premium product
- Environmental Disclosure:
- ENVPEP2206027EN
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Product Or Component Type:
- circuit breaker
- Color:
- Black
- Product Certifications:
- UL || CSA || NOM
- Eu Rohs Directive:
- Compliant with Exemptions
- Mercury Free:
- Yes
- Circuit Breaker Application:
- HACR rated
- Trip Unit Technology:
- thermal-magnetic
- Terminal Identifier:
- AL150HD
- Rohs Exemption Information:
- Yes
- Line Rated Current:
- 125-125 A
- Quality Labels:
- CE
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Pollution Degree:
- 3 IEC 60947-1
- Magnetic Hold Current:
- 900 A
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Communication Interface:
- Modbus || Ethernet
- Continuous Current Rating:
- 0.8
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Range:
- PowerPact
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Circularity Profile:
- ENVEOLI2206027EN
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Mounting Support:
- lug
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Control Type:
- toggle
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Wire Stripping Length:
- 16 mm
- Electrical Connection:
- lugs, line || lugs, load
- Pvc Free:
- Yes
- Magnetic Tripping Current:
- 1700-1700 A
- QN-QUOTE-REQUEST:
- true