- Pollution Degree:
- 3 IEC 60947-1
- Line Rated Current:
- 150-150 A
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Warranty:
- 18 months
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Product Certifications:
- UL || CSA || NOM
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2, LI
- Network Frequency:
- 50/60 Hz
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Utilisation Category:
- category A
- Net Weight:
- 2.2 kg
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Poles Description:
- 3P
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Width:
- 104 mm
- Mounting Support:
- lug
- Color:
- Black
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Protected Poles Description:
- 3t
- Terminal Identifier:
- AL150HD
- Product Or Component Type:
- circuit breaker
- Trip Unit Name:
- MicroLogic 3.2
- Product Name:
- PowerPact H
- Mounting Mode:
- unit mount lug)
- Ambient Air Temperature For Storage:
- -50-85 °C
- Communication Interface:
- Modbus || Ethernet
- Rohs Exemption Information:
- Yes
- Control Type:
- toggle
- Continuous Current Rating:
- 0.8
- Quantity Per Set:
- 1
- Pvc Free:
- Yes
- Wire Stripping Length:
- 16 mm
- Environmental Disclosure:
- ENVPEP2206028EN
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- Circularity Profile:
- ENVEOLI2206028EN
- Depth:
- 86 mm
- Mercury Free:
- Yes
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Quality Labels:
- CE
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Suitability For Isolation:
- yes IEC 60947-2
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Electrical Connection:
- lugs, line || lugs, load
- Range:
- PowerPact
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Height:
- 163 mm
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Ambient Air Temperature For Operation:
- -2-70 °C
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Sustainable Offer Status:
- Green Premium product
- Breaking Capacity Code:
- D
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Device Application:
- distribution
- QN-QUOTE-REQUEST:
- true