- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Protected Poles Description:
- 2t
- Mercury Free:
- Yes
- Magnetic Hold Current:
- 350 A
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Warranty:
- 18 months
- Control Type:
- toggle
- Mounting Support:
- bracket
- Depth:
- 86 mm
- Sustainable Offer Status:
- Green Premium product
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Line Rated Current:
- 20-20 A
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Trip Unit Technology:
- thermal-magnetic
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Continuous Current Rating:
- 0.8
- Product Name:
- PowerPact H
- Mounting Height:
- 3 in
- Pvc Free:
- Yes
- Mounting Mode:
- I-Line bracket)
- Quality Labels:
- CE
- Suitability For Isolation:
- yes IEC 60947-2
- Height:
- 163 mm
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Color:
- Black
- Utilisation Category:
- category A
- Magnetic Tripping Current:
- 750-750 A
- Wire Stripping Length:
- 16 mm
- Range:
- PowerPact
- Terminal Identifier:
- AL150HD
- Communication Interface:
- Modbus || Ethernet
- Product Or Component Type:
- circuit breaker
- Pollution Degree:
- 3 IEC 60947-1
- Quantity Per Set:
- 1
- Eu Rohs Directive:
- Compliant with Exemptions
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Net Weight:
- 2.2 kg
- Network Frequency:
- 50/60 Hz
- Breaking Capacity Code:
- G
- Poles Description:
- 2P
- Environmental Disclosure:
- ENVPEP2206027EN
- Width:
- 104 mm
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Circuit Breaker Application:
- HACR rated
- Electrical Connection:
- I-Line connection, line || lugs, load
- Device Application:
- distribution
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Rohs Exemption Information:
- Yes
- Circularity Profile:
- ENVEOLI2206027EN
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Phase Connection:
- BC
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Ambient Air Temperature For Storage:
- -50-85 °C
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Ambient Air Temperature For Operation:
- -2-70 °C
- Product Certifications:
- UL || CSA || NOM