- Depth:
- 86 mm
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Ambient Air Temperature For Operation:
- -2-70 °C
- Quantity Per Set:
- 1
- Magnetic Hold Current:
- 350 A
- Height:
- 163 mm
- Net Weight:
- 2.2 kg
- Phase Connection:
- CB
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Circuit Breaker Application:
- HACR rated
- Product Name:
- PowerPact H
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Communication Interface:
- Modbus || Ethernet
- Mounting Mode:
- I-Line bracket)
- Eu Rohs Directive:
- Compliant with Exemptions
- Ambient Air Temperature For Storage:
- -50-85 °C
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Wire Stripping Length:
- 16 mm
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Circularity Profile:
- ENVEOLI2206027EN
- Mounting Height:
- 3 in
- Protected Poles Description:
- 2t
- Poles Description:
- 2P
- Pvc Free:
- Yes
- Network Frequency:
- 50/60 Hz
- Rohs Exemption Information:
- Yes
- Warranty:
- 18 months
- Suitability For Isolation:
- yes IEC 60947-2
- Terminal Identifier:
- AL150HD
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Sustainable Offer Status:
- Green Premium product
- Color:
- Black
- Line Rated Current:
- 30-30 A
- Product Or Component Type:
- circuit breaker
- Utilisation Category:
- category A
- Magnetic Tripping Current:
- 750-750 A
- Electrical Connection:
- I-Line connection, line || lugs, load
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Trip Unit Technology:
- thermal-magnetic
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Continuous Current Rating:
- 0.8
- Pollution Degree:
- 3 IEC 60947-1
- Device Application:
- distribution
- Control Type:
- toggle
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Breaking Capacity Code:
- G
- Mercury Free:
- Yes
- Width:
- 104 mm
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Range:
- PowerPact
- Environmental Disclosure:
- ENVPEP2206027EN
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Mounting Support:
- bracket
- Quality Labels:
- CE