Schneider Electric HGA260401 Molded Case Circuit Breaker 600V 40A

(No reviews yet) Write a Review
SKU:
HGA260401
UPC:
785901539599
Condition:
New
Control Type:
toggle
Warranty:
18 months
Phase Connection:
AB
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Mounting Height:
3 in
Pvc Free:
Yes
Net Weight:
2.2 kg
Circularity Profile:
ENVEOLI2206027EN
Quality Labels:
CE
Product Certifications:
UL || CSA || NOM
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Ambient Air Temperature For Storage:
-50-85 °C
Range:
PowerPact
Environmental Disclosure:
ENVPEP2206027EN
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Electrical Connection:
I-Line connection, line || lugs, load
Height:
163 mm
Depth:
86 mm
Quantity Per Set:
1
Circuit Breaker Application:
HACR rated
Poles Description:
2P
Terminal Identifier:
AL150HD
Magnetic Tripping Current:
850-850 A
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Product Or Component Type:
circuit breaker
Wire Stripping Length:
16 mm
Pollution Degree:
3 IEC 60947-1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Width:
104 mm
Device Application:
distribution
Magnetic Hold Current:
400 A
Product Name:
PowerPact H
Communication Interface:
Modbus || Ethernet
Network Frequency:
50/60 Hz
Breaking Capacity Code:
G
Ambient Air Temperature For Operation:
-2-70 °C
Continuous Current Rating:
0.8
Mounting Mode:
I-Line bracket)
Sustainable Offer Status:
Green Premium product
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Color:
Black
Line Rated Current:
40-40 A
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Ip Degree Of Protection:
front cover IP40 IEC 60529
Local Signalling:
switched off (OFF) 1 trip indicator green)
Utilisation Category:
category A
Protected Poles Description:
2t
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Mercury Free:
Yes
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Rohs Exemption Information:
Yes
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Suitability For Isolation:
yes IEC 60947-2
Mounting Support:
bracket
Eu Rohs Directive:
Compliant with Exemptions
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Trip Unit Technology:
thermal-magnetic
$1,338.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 40A, 2 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an AB phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose