- Electrical Connection:
- lugs, line || lugs, load
- Pvc Free:
- Yes
- Breaking Capacity Code:
- G
- Quantity Per Set:
- 1
- Width:
- 104 mm
- Suitability For Isolation:
- yes IEC 60947-2
- Quality Labels:
- CE
- Magnetic Tripping Current:
- 1700-1700 A
- Circuit Breaker Application:
- HACR rated
- Height:
- 163 mm
- Environmental Disclosure:
- ENVPEP1311006EN
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Pollution Degree:
- 3 IEC 60947-1
- Sustainable Offer Status:
- Green Premium product
- Control Type:
- toggle
- Protected Poles Description:
- 3t
- Poles Description:
- 3P
- Mounting Support:
- lug
- Depth:
- 86 mm
- Terminal Identifier:
- AL150HD
- Color:
- Black
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Mercury Free:
- Yes
- Communication Interface:
- Modbus || Ethernet
- Ambient Air Temperature For Storage:
- -50-85 °C
- Product Certifications:
- UL || CSA || NOM
- Mounting Mode:
- unit mount lug)
- Net Weight:
- 2.2 kg
- Product Name:
- PowerPact H
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Utilisation Category:
- category A
- Eu Rohs Directive:
- Compliant
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Ambient Air Temperature For Operation:
- -2-70 °C
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Line Rated Current:
- 100-100 A
- Circularity Profile:
- ENVEOLI1311006EN
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Magnetic Hold Current:
- 900 A
- Range:
- PowerPact
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Wire Stripping Length:
- 16 mm
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Warranty:
- 18 months
- Trip Unit Technology:
- thermal-magnetic
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Accessory / Separate Part Type:
- auxiliary switch 24 V AC/DC 1 NO + 1 NC cover frame
- Continuous Current Rating:
- 0.8
- Product Or Component Type:
- circuit breaker
- Device Application:
- distribution
- Network Frequency:
- 50/60 Hz
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Rohs Exemption Information:
- Yes