Line Rated Current:
100-100 A
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Circularity Profile:
ENVEOLI2206028EN
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Mercury Free:
Yes
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Device Application:
distribution
Product Certifications:
UL || CSA || NOM
Mounting Support:
lug
Communication Interface:
Modbus || Ethernet
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Ambient Air Temperature For Operation:
-2-70 °C
Poles Description:
3P
Circuit Breaker Application:
HACR rated
Continuous Current Rating:
1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Local Signalling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
Warranty:
18 months
Width:
104 mm
Rohs Exemption Information:
Yes
Net Weight:
2.2 kg
Trip Unit Technology:
electronic, standard, MicroLogic 3.2, LI
Suitability For Isolation:
yes IEC 60947-2
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Ambient Air Temperature For Storage:
-50-85 °C
Electrical Connection:
lugs, line || lugs, load
Environmental Disclosure:
ENVPEP2206028EN
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Utilisation Category:
category A
Quality Labels:
CE
Network Frequency:
50/60 Hz
Pollution Degree:
3 IEC 60947-1
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Trip Unit Name:
MicroLogic 3.2
Mounting Mode:
unit mount lug)
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Wire Stripping Length:
16 mm
Eu Rohs Directive:
Compliant with Exemptions
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Color:
Black
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Product Or Component Type:
circuit breaker
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Pvc Free:
Yes
Depth:
86 mm
Control Type:
toggle
Product Name:
PowerPact H
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Quantity Per Set:
1
Breaking Capacity Code:
G
Ip Degree Of Protection:
front cover IP40 IEC 60529
Terminal Identifier:
AL150HD
Sustainable Offer Status:
Green Premium product
Range:
PowerPact
Protected Poles Description:
3t
Height:
163 mm
Brochure:
View
Catalog:
View
Datasheet:
View
$2,171.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides Micrologic Standard with a 3.2 trip unit and an LI function with a breaking capacity of 18kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT H, 100A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 100%. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.