- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Terminal Identifier:
- AL150HD
- Wire Stripping Length:
- 16 mm
- Mounting Mode:
- unit mount lug)
- Network Frequency:
- 50/60 Hz
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Width:
- 104 mm
- Line Rated Current:
- 150-150 A
- Height:
- 163 mm
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Product Name:
- PowerPact H
- Mercury Free:
- Yes
- Quantity Per Set:
- 1
- Utilisation Category:
- category A
- Range:
- PowerPact
- Protected Poles Description:
- 3t
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Control Type:
- toggle
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Depth:
- 86 mm
- Ambient Air Temperature For Operation:
- -2-70 °C
- Color:
- Black
- Electrical Connection:
- lugs, line || lugs, load
- Continuous Current Rating:
- 1
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Product Or Component Type:
- circuit breaker
- Pollution Degree:
- 3 IEC 60947-1
- Mounting Support:
- lug
- Product Certifications:
- UL || CSA || NOM
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Warranty:
- 18 months
- Quality Labels:
- CE
- Poles Description:
- 3P
- Device Application:
- distribution
- Pvc Free:
- Yes
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Ambient Air Temperature For Storage:
- -50-85 °C
- Trip Unit Name:
- MicroLogic 3.2 S
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Environmental Disclosure:
- ENVPEP2206028EN
- Net Weight:
- 2.2 kg
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2 S, LSI
- Sustainable Offer Status:
- Green Premium product
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Circularity Profile:
- ENVEOLI2206028EN
- Suitability For Isolation:
- yes IEC 60947-2
- Rohs Exemption Information:
- Yes
- Eu Rohs Directive:
- Compliant with Exemptions
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Breaking Capacity Code:
- G
- Communication Interface:
- Modbus || Ethernet
- QN-QUOTE-REQUEST:
- true