Schneider Electric HGL36150SA Molded Case Circuit Breaker 600V 150A

(No reviews yet) Write a Review
SKU:
HGL36150SA
UPC:
785901676928
Condition:
New
Depth:
86 mm
Local Signalling:
switched off (OFF) 1 trip indicator green)
Width:
104 mm
Color:
Black
Ambient Air Temperature For Operation:
-2-70 °C
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Range:
PowerPact
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Protected Poles Description:
3t
Sustainable Offer Status:
Green Premium product
Environmental Disclosure:
ENVPEP2206027EN
Poles Description:
3P
Pollution Degree:
3 IEC 60947-1
Breaking Capacity Code:
G
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Communication Interface:
Modbus || Ethernet
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Wire Stripping Length:
16 mm
Terminal Identifier:
AL150HD
Suitability For Isolation:
yes IEC 60947-2
Mounting Mode:
unit mount lug)
Quality Labels:
CE
Accessory / Separate Part Type:
shunt trip 110...130 V AC compartment
Mercury Free:
Yes
Electrical Connection:
lugs, line || lugs, load
Magnetic Hold Current:
900 A
Control Type:
toggle
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Trip Unit Technology:
thermal-magnetic
Height:
163 mm
Eu Rohs Directive:
Compliant with Exemptions
Line Rated Current:
150-150 A
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Utilisation Category:
category A
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Circularity Profile:
ENVEOLI2206027EN
Device Application:
distribution
Circuit Breaker Application:
HACR rated
Pvc Free:
Yes
Magnetic Tripping Current:
1700-1700 A
Continuous Current Rating:
0.8
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Net Weight:
2.2 kg
Product Name:
PowerPact H
Product Certifications:
UL || CSA || NOM
Rohs Exemption Information:
Yes
Mounting Support:
lug
Network Frequency:
50/60 Hz
Quantity Per Set:
1
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Product Or Component Type:
circuit breaker
Ambient Air Temperature For Storage:
-50-85 °C
Ip Degree Of Protection:
front cover IP40 IEC 60529
Warranty:
18 months
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
$4,316.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT H, 150A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. This unit includes a factory installed 120VAC shunt trip. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose