- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Environmental Disclosure:
- ENVPEP2206028EN
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Line Rated Current:
- 150-150 A
- Utilisation Category:
- category A
- Ambient Air Temperature For Storage:
- -50-85 °C
- Product Or Component Type:
- circuit breaker
- Control Type:
- toggle
- Eu Rohs Directive:
- Compliant with Exemptions
- Pvc Free:
- Yes
- Net Weight:
- 2.2 kg
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2, LI
- Mercury Free:
- Yes
- Suitability For Isolation:
- yes IEC 60947-2
- Pollution Degree:
- 3 IEC 60947-1
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Mounting Mode:
- unit mount lug)
- Mounting Support:
- lug
- Depth:
- 86 mm
- Trip Unit Name:
- MicroLogic 3.2
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Poles Description:
- 3P
- Quantity Per Set:
- 1
- Product Name:
- PowerPact H
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Communication Interface:
- Modbus || Ethernet
- Network Frequency:
- 50/60 Hz
- Quality Labels:
- CE
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Range:
- PowerPact
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Continuous Current Rating:
- 0.8
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Width:
- 104 mm
- Terminal Identifier:
- AL150HD
- Rohs Exemption Information:
- Yes
- Height:
- 163 mm
- Wire Stripping Length:
- 16 mm
- Protected Poles Description:
- 3t
- Electrical Connection:
- lugs, line || lugs, load
- Sustainable Offer Status:
- Green Premium product
- Ambient Air Temperature For Operation:
- -2-70 °C
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Circuit Breaker Application:
- HACR rated
- Circularity Profile:
- ENVEOLI2206028EN
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Device Application:
- distribution
- Warranty:
- 18 months
- Color:
- Black
- Breaking Capacity Code:
- G
- QN-QUOTE-REQUEST:
- true