Schneider Electric HJA260151 Molded Case Circuit Breaker 600V 15A

(No reviews yet) Write a Review
SKU:
HJA260151
UPC:
7.85902E+11
Condition:
New
Electrical Connection:
I-Line connection, line || lugs, load
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Control Type:
toggle
Trip Unit Technology:
thermal-magnetic
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Environmental Disclosure:
ENVPEP2206027EN
Poles Description:
2P
Sustainable Offer Status:
Green Premium product
Width:
104 mm
Protected Poles Description:
2t
Ip Degree Of Protection:
front cover IP40 IEC 60529
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Product Certifications:
UL || CSA || NOM
Wire Stripping Length:
16 mm
Breaking Capacity Code:
J
Network Frequency:
50/60 Hz
Product Or Component Type:
circuit breaker
Magnetic Tripping Current:
750-750 A
Phase Connection:
AB
Color:
Black
Suitability For Isolation:
yes IEC 60947-2
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Ambient Air Temperature For Operation:
-2-70 °C
Ambient Air Temperature For Storage:
-50-85 °C
Warranty:
18 months
Product Name:
PowerPact H
Terminal Identifier:
AL150HD
Eu Rohs Directive:
Compliant with Exemptions
Height:
163 mm
Circuit Breaker Application:
HACR rated
Utilisation Category:
category A
Mercury Free:
Yes
Local Signalling:
switched off (OFF) 1 trip indicator green)
[Ics] Rated Service Breaking Capacity:
100 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 65 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 25 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Pollution Degree:
3 IEC 60947-1
Mounting Mode:
I-Line bracket)
Pvc Free:
Yes
Range:
PowerPact
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Magnetic Hold Current:
350 A
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Net Weight:
2.2 kg
Device Application:
distribution
Mounting Height:
4.5 in
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Depth:
86 mm
Rohs Exemption Information:
Yes
Quantity Per Set:
1
Quality Labels:
CE
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Breaking Capacity:
100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
Continuous Current Rating:
0.8
Circularity Profile:
ENVEOLI2206027EN
Mounting Support:
bracket
Line Rated Current:
15-15 A
Communication Interface:
Modbus || Ethernet
Brochure:
View
Catalog:
View
Datasheet:
View
  • Schneider Electric HJA260151 Molded Case Circuit Breaker 600V 15A
  • Schneider Electric HJA260151 Molded Case Circuit Breaker 600V 15A
$1,589.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 25kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 15A, 2 pole, circuit breaker has a breaking capacity of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an AB phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.