- Rohs Exemption Information:
- Yes
- Utilisation Category:
- category A
- Mercury Free:
- Yes
- Circuit Breaker Application:
- HACR rated
- Sustainable Offer Status:
- Green Premium product
- Range:
- PowerPact
- Environmental Disclosure:
- ENVPEP2206027EN
- Width:
- 104 mm
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Net Weight:
- 2.2 kg
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Line Rated Current:
- 20-20 A
- Continuous Current Rating:
- 0.8
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Ambient Air Temperature For Storage:
- -50-85 °C
- Electrical Connection:
- I-Line connection, line || lugs, load
- Mounting Height:
- 4.5 in
- Mounting Mode:
- I-Line bracket)
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Quantity Per Set:
- 1
- Magnetic Hold Current:
- 350 A
- Device Application:
- distribution
- Color:
- Black
- Network Frequency:
- 50/60 Hz
- Product Certifications:
- UL || CSA || NOM
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Phase Connection:
- BC
- Product Name:
- PowerPact H
- Product Or Component Type:
- circuit breaker
- Mounting Support:
- bracket
- Suitability For Isolation:
- yes IEC 60947-2
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Quality Labels:
- CE
- Terminal Identifier:
- AL150HD
- Warranty:
- 18 months
- Wire Stripping Length:
- 16 mm
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Ambient Air Temperature For Operation:
- -2-70 °C
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Depth:
- 86 mm
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Control Type:
- toggle
- Protected Poles Description:
- 2t
- Trip Unit Technology:
- thermal-magnetic
- Pvc Free:
- Yes
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Circularity Profile:
- ENVEOLI2206027EN
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Breaking Capacity Code:
- J
- Height:
- 163 mm
- Communication Interface:
- Modbus || Ethernet
- [Ics] Rated Service Breaking Capacity:
- 100 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 65 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 25 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- Magnetic Tripping Current:
- 750-750 A
- Poles Description:
- 2P
- Pollution Degree:
- 3 IEC 60947-1
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- QN-QUOTE-REQUEST: