- Control Type:
- toggle
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Eu Rohs Directive:
- Compliant with Exemptions
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Network Frequency:
- 50/60 Hz
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Product Name:
- PowerPact H
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Electrical Connection:
- lugs, line || lugs, load
- Quality Labels:
- CE
- Magnetic Tripping Current:
- 750-750 A
- Rohs Exemption Information:
- Yes
- Breaking Capacity Code:
- J
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Circuit Breaker Application:
- HACR rated
- Terminal Identifier:
- AL150HD
- Device Application:
- distribution
- Utilisation Category:
- category A
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Quantity Per Set:
- 1
- Protected Poles Description:
- 3t
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Circularity Profile:
- ENVEOLI2206027EN
- Depth:
- 86 mm
- Suitability For Isolation:
- yes IEC 60947-2
- Ambient Air Temperature For Operation:
- -2-70 °C
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Magnetic Hold Current:
- 350 A
- Warranty:
- 18 months
- Environmental Disclosure:
- ENVPEP2206027EN
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Trip Unit Technology:
- thermal-magnetic
- Pollution Degree:
- 3 IEC 60947-1
- Poles Description:
- 3P
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Line Rated Current:
- 20-20 A
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Wire Stripping Length:
- 16 mm
- Sustainable Offer Status:
- Green Premium product
- Mounting Support:
- lug
- Net Weight:
- 2.2 kg
- Height:
- 163 mm
- Ambient Air Temperature For Storage:
- -50-85 °C
- Product Or Component Type:
- circuit breaker
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Product Certifications:
- UL || CSA || NOM
- Width:
- 104 mm
- Continuous Current Rating:
- 0.8
- Mounting Mode:
- unit mount lug)
- Range:
- PowerPact
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Communication Interface:
- Modbus || Ethernet
- Pvc Free:
- Yes
- Mercury Free:
- Yes
- Color:
- Black