- Depth:
- 86 mm
- Poles Description:
- 3P
- Pollution Degree:
- 3 IEC 60947-1
- Trip Unit Technology:
- thermal-magnetic
- Communication Interface:
- Modbus || Ethernet
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Breaking Capacity Code:
- J
- Ambient Air Temperature For Storage:
- -50-85 °C
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Range:
- PowerPact
- Ambient Air Temperature For Operation:
- -2-70 °C
- Mounting Mode:
- unit mount lug)
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Warranty:
- 18 months
- Eu Rohs Directive:
- Compliant with Exemptions
- Environmental Disclosure:
- ENVPEP2206027EN
- Terminal Identifier:
- AL150HD
- Control Type:
- toggle
- Circuit Breaker Application:
- HACR rated
- Mounting Support:
- lug
- Pvc Free:
- Yes
- Network Frequency:
- 50/60 Hz
- Sustainable Offer Status:
- Green Premium product
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Quantity Per Set:
- 1
- Net Weight:
- 2.2 kg
- Product Or Component Type:
- circuit breaker
- Continuous Current Rating:
- 0.8
- Magnetic Tripping Current:
- 1700-1700 A
- Utilisation Category:
- category A
- Quality Labels:
- CE
- Product Certifications:
- UL || CSA || NOM
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Circularity Profile:
- ENVEOLI2206027EN
- Width:
- 104 mm
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Wire Stripping Length:
- 16 mm
- Mercury Free:
- Yes
- Height:
- 163 mm
- Electrical Connection:
- lugs, line || lugs, load
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Rohs Exemption Information:
- Yes
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Suitability For Isolation:
- yes IEC 60947-2
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Line Rated Current:
- 150-150 A
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Device Application:
- distribution
- Magnetic Hold Current:
- 900 A
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Color:
- Black
- Product Name:
- PowerPact H
- Protected Poles Description:
- 3t