- Quantity Per Set:
- 1
- Suitability For Isolation:
- yes IEC 60947-2
- Color:
- Black
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Wire Stripping Length:
- 16 mm
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Control Type:
- toggle
- Product Or Component Type:
- circuit breaker
- Depth:
- 86 mm
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile:
- ENVEOLI2206028EN
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Trip Unit Technology:
- electronic, energy, MicroLogic 5.2 E, LSI
- Rohs Exemption Information:
- Yes
- Product Name:
- PowerPact H
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Net Weight:
- 2.2 kg
- Poles Description:
- 3P
- Mounting Support:
- lug
- Height:
- 163 mm
- Ambient Air Temperature For Operation:
- -2-70 °C
- Range:
- PowerPact
- Product Certifications:
- UL || CSA || NOM
- Line Rated Current:
- 150-150 A
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Terminal Identifier:
- AL150HD
- Warranty:
- 18 months
- Circuit Breaker Application:
- HACR rated
- Eu Rohs Directive:
- Compliant with Exemptions
- Protected Poles Description:
- 3t
- Network Frequency:
- 50/60 Hz
- Trip Unit Name:
- MicroLogic 5.2 E
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Environmental Disclosure:
- ENVPEP2206028EN
- Width:
- 104 mm
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Breaking Capacity Code:
- J
- Communication Interface:
- Modbus || Ethernet
- Ambient Air Temperature For Storage:
- -50-85 °C
- Device Application:
- distribution
- Pvc Free:
- Yes
- Pollution Degree:
- 3 IEC 60947-1
- Sustainable Offer Status:
- Green Premium product
- Mounting Mode:
- unit mount lug)
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Mercury Free:
- Yes
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Continuous Current Rating:
- 1
- Electrical Connection:
- lugs, line || lugs, load
- Quality Labels:
- CE
- Utilisation Category:
- category A
- QN-QUOTE-REQUEST:
- true