- Utilisation Category:
- category A
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2, LI
- Poles Description:
- 3P
- Product Name:
- PowerPact H
- Pvc Free:
- Yes
- Mounting Mode:
- unit mount lug)
- Net Weight:
- 2.2 kg
- Breaking Capacity:
- 200 kA 240 V AC 50/60 Hz UL 489 || 200 kA 480 V AC 50/60 Hz UL 489 || 100 kA 600 V AC 50/60 Hz UL 489
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Communication Interface:
- Modbus || Ethernet
- Continuous Current Rating:
- 1
- Product Certifications:
- UL || CSA || NOM
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Circularity Profile:
- ENVEOLI2206028EN
- Electrical Connection:
- lugs, line || lugs, load
- Quality Labels:
- CE
- Color:
- Black
- Line Rated Current:
- 60-60 A
- Range:
- PowerPact
- Control Type:
- toggle
- Suitability For Isolation:
- yes IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Breaking Capacity Code:
- R
- Protected Poles Description:
- 3t
- Pollution Degree:
- 3 IEC 60947-1
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Eu Rohs Directive:
- Compliant with Exemptions
- Quantity Per Set:
- 1
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Rohs Exemption Information:
- Yes
- Product Or Component Type:
- circuit breaker
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Wire Stripping Length:
- 16 mm
- Ambient Air Temperature For Operation:
- -2-70 °C
- Mercury Free:
- Yes
- Environmental Disclosure:
- ENVPEP2206028EN
- Ambient Air Temperature For Storage:
- -50-85 °C
- Mounting Support:
- lug
- Terminal Identifier:
- AL150HD
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Network Frequency:
- 50/60 Hz
- Sustainable Offer Status:
- Green Premium product
- Width:
- 104 mm
- Trip Unit Name:
- MicroLogic 3.2
- Depth:
- 86 mm
- Device Application:
- distribution
- Height:
- 163 mm
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- [Ics] Rated Service Breaking Capacity:
- 150 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 125 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 75 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 690 V AC 50/60 Hz IEC 60947-2