- Electrical Connection:
- I-Line connection, line || lugs, load
- Pollution Degree:
- 3 IEC 60947-1
- Product Or Component Type:
- circuit breaker
- Magnetic Tripping Current:
- 2000-2000 A
- Warranty:
- 18 months
- Environmental Disclosure:
- ENVPEP2206031EN
- Terminal Identifier:
- AL250JD
- Depth:
- 86 mm
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Quality Labels:
- CE
- Ambient Air Temperature For Storage:
- -50-85 °C
- Accessory / Separate Part Type:
- shunt trip 110...130 V AC compartment
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Communication Interface:
- Modbus || Ethernet
- Poles Description:
- 3P
- Ambient Air Temperature For Operation:
- -2-70 °C
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Eu Rohs Directive:
- Compliant with Exemptions
- Continuous Current Rating:
- 0.8
- Mounting Support:
- bracket
- Net Weight:
- 2.4 kg
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Trip Unit Technology:
- thermal-magnetic
- Product Certifications:
- UL || CSA || NOM
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Control Type:
- toggle
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Circularity Profile:
- ENVEOLI2206031EN
- Sustainable Offer Status:
- Green Premium product
- Product Name:
- PowerPact J
- Utilisation Category:
- category A
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Ip Degree Of Protection:
- front cover IP40
- Network Frequency:
- 50/60 Hz
- Mounting Mode:
- I-Line bracket)
- Breaking Capacity Code:
- D
- Range:
- PowerPact
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Mounting Height:
- 4.5 in
- Pvc Free:
- Yes
- Device Application:
- distribution
- Line Rated Current:
- 200-200 A
- Mercury Free:
- Yes
- Wire Stripping Length:
- 25 mm
- Magnetic Hold Current:
- 1000 A
- Suitability For Isolation:
- yes IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Rohs Exemption Information:
- Yes
- Width:
- 104 mm
- Protection Type:
- overload protection || short-circuit protection
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Height:
- 191 mm