Schneider Electric JDA36200SA Molded Case Circuit Breaker 600V 200A

(No reviews yet) Write a Review
SKU:
JDA36200SA
UPC:
785901493273
Condition:
New
Electrical Connection:
I-Line connection, line || lugs, load
Pollution Degree:
3 IEC 60947-1
Product Or Component Type:
circuit breaker
Magnetic Tripping Current:
2000-2000 A
Warranty:
18 months
Environmental Disclosure:
ENVPEP2206031EN
Terminal Identifier:
AL250JD
Depth:
86 mm
[Ics] Rated Service Breaking Capacity:
25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Quality Labels:
CE
Ambient Air Temperature For Storage:
-50-85 °C
Accessory / Separate Part Type:
shunt trip 110...130 V AC compartment
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Awg Gauge:
AWG 3/0...350 kcmil aluminium/copper terminals
Communication Interface:
Modbus || Ethernet
Poles Description:
3P
Ambient Air Temperature For Operation:
-2-70 °C
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Breaking Capacity:
25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
Eu Rohs Directive:
Compliant with Exemptions
Continuous Current Rating:
0.8
Mounting Support:
bracket
Net Weight:
2.4 kg
Local Signalling:
switched off (OFF) 1 trip indicator green)
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Trip Unit Technology:
thermal-magnetic
Product Certifications:
UL || CSA || NOM
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Control Type:
toggle
Tightening Torque:
25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
Circularity Profile:
ENVEOLI2206031EN
Sustainable Offer Status:
Green Premium product
Product Name:
PowerPact J
Utilisation Category:
category A
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Ip Degree Of Protection:
front cover IP40
Network Frequency:
50/60 Hz
Mounting Mode:
I-Line bracket)
Breaking Capacity Code:
D
Range:
PowerPact
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Mounting Height:
4.5 in
Pvc Free:
Yes
Device Application:
distribution
Line Rated Current:
200-200 A
Mercury Free:
Yes
Wire Stripping Length:
25 mm
Magnetic Hold Current:
1000 A
Suitability For Isolation:
yes IEC 60947-2
Circuit Breaker Application:
HACR rated
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Rohs Exemption Information:
Yes
Width:
104 mm
Protection Type:
overload protection || short-circuit protection
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Height:
191 mm
Brochure:
View
Catalog:
View
Datasheet:
View
$3,584.00

Description

PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT J I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT J, 200A, 3 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. This unit includes a factory installed 120VAC shunt trip. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose