- Warranty:
- 18 months
- Product Name:
- PowerPact J
- Mounting Support:
- bracket
- Quality Labels:
- CE
- Environmental Disclosure:
- ENVPEP2206032EN
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Control Type:
- toggle
- Mercury Free:
- Yes
- Net Weight:
- 2.4 kg
- Breaking Capacity Code:
- D
- Range:
- PowerPact
- Continuous Current Rating:
- 0.8
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Device Application:
- distribution
- Terminal Identifier:
- AL250JD
- Height:
- 191 mm
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Pollution Degree:
- 3 IEC 60947-1
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Utilisation Category:
- category A
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Poles Description:
- 3P
- Rohs Exemption Information:
- Yes
- Product Or Component Type:
- circuit breaker
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Sustainable Offer Status:
- Green Premium product
- Ambient Air Temperature For Operation:
- -2-70 °C
- Eu Rohs Directive:
- Compliant with Exemptions
- Ambient Air Temperature For Storage:
- -50-85 °C
- Width:
- 104 mm
- Product Certifications:
- UL || CSA || NOM
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm 1 LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Network Frequency:
- 50/60 Hz
- Ip Degree Of Protection:
- front cover IP40
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2 S, LSI
- Phase Connection:
- CA
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Depth:
- 86 mm
- Suitability For Isolation:
- yes IEC 60947-2
- Pvc Free:
- Yes
- Circularity Profile:
- ENVEOLI2206032EN
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Wire Stripping Length:
- 25 mm
- Trip Unit Name:
- MicroLogic 3.2 S
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Circuit Breaker Application:
- HACR rated
- Protection Type:
- overload protection || short-circuit protection
- Mounting Height:
- 4.5 in
- Electrical Connection:
- I-Line connection, line || lugs, load
- Communication Interface:
- Modbus || Ethernet
- Line Rated Current:
- 250-250 A
- Mounting Mode:
- I-Line bracket)