Schneider Electric JDF36200 Molded Case Circuit Breaker 600V 200A
Schneider Electric
$2,730.00
PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has a busbar connection. This PowerPacT J, 200A, 3 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Sustainable Offer Status:
- Green Premium product
- Height:
- 191 mm
- Product Certifications:
- UL || CSA || NOM
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Warranty:
- 18 months
- Rohs Exemption Information:
- Yes
- Protection Type:
- overload protection || short-circuit protection
- Net Weight:
- 2.4 kg
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Width:
- 104 mm
- Utilisation Category:
- category A
- Network Frequency:
- 50/60 Hz
- Depth:
- 86 mm
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Terminal Identifier:
- AL250JD
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Trip Unit Technology:
- thermal-magnetic
- Phase Connection:
- BA
- Poles Description:
- 3P
- Circuit Breaker Application:
- HACR rated
- Breaking Capacity Code:
- D
- Range:
- PowerPact
- Pvc Free:
- Yes
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Magnetic Hold Current:
- 1000 A
- Ambient Air Temperature For Operation:
- -2-70 °C
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Product Name:
- PowerPact J
- Circularity Profile:
- ENVEOLI2206031EN
- Mounting Mode:
- unit mount busbar)
- Ambient Air Temperature For Storage:
- -50-85 °C
- Mounting Height:
- 4.5 in
- Product Or Component Type:
- circuit breaker
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Suitability For Isolation:
- yes IEC 60947-2
- Magnetic Tripping Current:
- 2000-2000 A
- Environmental Disclosure:
- ENVPEP2206031EN
- Device Application:
- distribution
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Wire Stripping Length:
- 25 mm
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Control Type:
- toggle
- Continuous Current Rating:
- 0.8
- Ip Degree Of Protection:
- front cover IP40
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Communication Interface:
- Modbus || Ethernet
- Line Rated Current:
- 200-200 A
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Quality Labels:
- CE
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Mounting Support:
- busbar
- Eu Rohs Directive:
- Compliant with Exemptions
- Pollution Degree:
- 3 IEC 60947-1
- Mercury Free:
- Yes
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View