- Magnetic Tripping Current:
- 1750-1750 A
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Mercury Free:
- Yes
- Environmental Disclosure:
- ENVPEP2206031EN
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Network Frequency:
- 50/60 Hz
- Rohs Exemption Information:
- Yes
- Quality Labels:
- CE
- Eu Rohs Directive:
- Compliant with Exemptions
- Suitability For Isolation:
- yes IEC 60947-2
- Control Type:
- toggle
- Awg Gauge:
- AWG 4...AWG 4/0 aluminium/copper terminal
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Ambient Air Temperature For Storage:
- -50-85 °C
- Mounting Mode:
- unit mount lug)
- Utilisation Category:
- category A
- Terminal Identifier:
- AL175JD
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Continuous Current Rating:
- 0.8
- Magnetic Hold Current:
- 750 A
- Depth:
- 86 mm
- Width:
- 104 mm
- Tightening Torque:
- 25-25 N.m 25-95 mm² (AWG 4...AWG 4/0)
- Warranty:
- 18 months
- Net Weight:
- 2.4 kg
- Range:
- PowerPact
- Circularity Profile:
- ENVEOLI2206031EN
- Ambient Air Temperature For Operation:
- -2-70 °C
- Height:
- 191 mm
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Line Rated Current:
- 150-150 A
- Circuit Breaker Application:
- HACR rated
- Poles Description:
- 2P
- Ip Degree Of Protection:
- front cover IP40
- Mounting Support:
- lug
- Communication Interface:
- Modbus || Ethernet
- Wire Stripping Length:
- 25 mm
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Pollution Degree:
- 3 IEC 60947-1
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Breaking Capacity Code:
- D
- Device Application:
- distribution
- Product Or Component Type:
- circuit breaker
- Product Name:
- PowerPact J
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Trip Unit Technology:
- thermal-magnetic
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Electrical Connection:
- lugs, line || lugs, load
- Pvc Free:
- Yes
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Protection Type:
- overload protection || short-circuit protection
- Sustainable Offer Status:
- Green Premium product