- Magnetic Tripping Current:
- 2000-2000 A
- Line Rated Current:
- 200-200 A
- Terminal Identifier:
- AL250JD
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Communication Interface:
- Modbus || Ethernet
- Range:
- PowerPact
- Pollution Degree:
- 3 IEC 60947-1
- Protection Type:
- overload protection || short-circuit protection
- Net Weight:
- 2.4 kg
- Trip Unit Technology:
- thermal-magnetic
- Magnetic Hold Current:
- 1000 A
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Height:
- 191 mm
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Width:
- 104 mm
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Warranty:
- 18 months
- Quality Labels:
- CE
- Mounting Support:
- lug
- Product Or Component Type:
- circuit breaker
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Rohs Exemption Information:
- Yes
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Control Type:
- toggle
- Device Application:
- distribution
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Wire Stripping Length:
- 25 mm
- Electrical Connection:
- terminal nut, line || lugs, load
- Mounting Mode:
- unit mount lug)
- Poles Description:
- 3P
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Continuous Current Rating:
- 0.8
- Ambient Air Temperature For Storage:
- -50-85 °C
- Eu Rohs Directive:
- Compliant with Exemptions
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Network Frequency:
- 50/60 Hz
- Breaking Capacity Code:
- D
- Environmental Disclosure:
- ENVPEP2206031EN
- Product Name:
- PowerPact J
- Depth:
- 86 mm
- Circuit Breaker Application:
- HACR rated
- Product Certifications:
- UL || CSA || NOM
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Mercury Free:
- Yes
- Ip Degree Of Protection:
- front cover IP40
- Circularity Profile:
- ENVEOLI2206031EN
- Utilisation Category:
- category A
- Sustainable Offer Status:
- Green Premium product
- Pvc Free:
- Yes
- Ambient Air Temperature For Operation:
- -2-70 °C
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Suitability For Isolation:
- yes IEC 60947-2