- Mounting Height:
- 4.5 in
- Product Certifications:
- UL || CSA || NOM
- Protection Type:
- overload protection || short-circuit protection
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Device Application:
- distribution
- Product Name:
- PowerPact J
- Mounting Mode:
- I-Line bracket)
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Breaking Capacity Code:
- G
- Warranty:
- 18 months
- Control Type:
- toggle
- Poles Description:
- 3P
- Sustainable Offer Status:
- Green Premium product
- Quality Labels:
- CE
- Electrical Connection:
- I-Line connection, line || lugs, load
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Terminal Identifier:
- AL175JD
- Circuit Breaker Application:
- HACR rated
- Communication Interface:
- Modbus || Ethernet
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Magnetic Tripping Current:
- 1750-1750 A
- Circularity Profile:
- ENVEOLI2206031EN
- Tightening Torque:
- 25-25 N.m 25-95 mm² (AWG 4...AWG 4/0)
- Phase Connection:
- ABC
- Utilisation Category:
- category A
- Trip Unit Technology:
- thermal-magnetic
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Range:
- PowerPact
- Rohs Exemption Information:
- Yes
- Wire Stripping Length:
- 25 mm
- Eu Rohs Directive:
- Compliant with Exemptions
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Width:
- 104 mm
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Mounting Support:
- bracket
- Product Or Component Type:
- circuit breaker
- Continuous Current Rating:
- 0.8
- Ip Degree Of Protection:
- front cover IP40
- Line Rated Current:
- 175-175 A
- Network Frequency:
- 50/60 Hz
- Environmental Disclosure:
- ENVPEP2206031EN
- Net Weight:
- 2.4 kg
- Pollution Degree:
- 3 IEC 60947-1
- Ambient Air Temperature For Operation:
- -2-70 °C
- Suitability For Isolation:
- yes IEC 60947-2
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Height:
- 191 mm
- Depth:
- 86 mm
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Pvc Free:
- Yes
- Mercury Free:
- Yes
- Magnetic Hold Current:
- 875 A
- Ambient Air Temperature For Storage:
- -50-85 °C
- Awg Gauge:
- AWG 4...AWG 4/0 aluminium/copper terminal