Schneider Electric JGA36250U53X Molded Case Circuit Breaker 600V 250A

(No reviews yet) Write a Review
SKU:
JGA36250U53X
UPC:
3606486072851
Condition:
New
Ambient Air Temperature For Operation:
-2-70 °C
Long Time Pick-Up Adjustment Range:
0.25...1 x In
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Network Frequency:
50/60 Hz
Product Or Component Type:
circuit breaker
Communication Interface:
Modbus || Ethernet
Local Signalling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm 1 LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
Circuit Breaker Application:
HACR rated
Continuous Current Rating:
0.8
Tightening Torque:
25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
Sustainable Offer Status:
Green Premium product
Line Rated Current:
250-250 A
Awg Gauge:
AWG 3/0...350 kcmil aluminium/copper terminals
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Trip Unit Name:
MicroLogic 5.2 E
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Wire Stripping Length:
25 mm
Breaking Capacity Code:
G
Mounting Height:
4.5 in
Product Name:
PowerPact J
Rohs Exemption Information:
Yes
Width:
104 mm
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Height:
191 mm
Net Weight:
2.4 kg
Quality Labels:
CE
Utilisation Category:
category A
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Device Application:
distribution
Protection Type:
overload protection || short-circuit protection
Pvc Free:
Yes
Mounting Support:
bracket
Ambient Air Temperature For Storage:
-50-85 °C
Suitability For Isolation:
yes IEC 60947-2
Control Type:
toggle
Circularity Profile:
ENVEOLI2206032EN
Trip Unit Technology:
electronic, energy, MicroLogic 5.2 E, LSI
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Depth:
86 mm
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Pollution Degree:
3 IEC 60947-1
Mounting Mode:
I-Line bracket)
Ip Degree Of Protection:
front cover IP40
Warranty:
18 months
Electrical Connection:
I-Line connection, line || lugs, load
Environmental Disclosure:
ENVPEP2206032EN
Range:
PowerPact
Poles Description:
3P
Terminal Identifier:
AL250JD
Product Certifications:
UL || CSA || NOM
Eu Rohs Directive:
Compliant with Exemptions
Mercury Free:
Yes
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Brochure:
View
Catalog:
View
Datasheet:
View
$5,947.00

Description

PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides Micrologic Energy with a 5.2E trip unit and an LSI function with a breaking capacity of 18kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT J I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT J, 250A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose