Schneider Electric JGL26150 Molded Case Circuit Breaker 600V 150A

(No reviews yet) Write a Review
SKU:
JGL26150
UPC:
7.85902E+11
Condition:
New
Local Signalling:
switched off (OFF) 1 trip indicator green)
Range:
PowerPact
Breaking Capacity Code:
G
Electrical Connection:
lugs, line || lugs, load
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Continuous Current Rating:
0.8
Tightening Torque:
25-25 N.m 25-95 mm² (AWG 4...AWG 4/0)
Eu Rohs Directive:
Compliant
Ambient Air Temperature For Storage:
-50-85 °C
Circularity Profile:
ENVEOLI1311008
Width:
104 mm
Mounting Mode:
unit mount lug)
Control Type:
toggle
Product Certifications:
UL || CSA || NOM
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Terminal Identifier:
AL175JD
Network Frequency:
50/60 Hz
Protection Type:
overload protection || short-circuit protection
Wire Stripping Length:
25 mm
Trip Unit Technology:
thermal-magnetic
Suitability For Isolation:
yes IEC 60947-2
Device Application:
distribution
Environmental Disclosure:
ENVPEP1311008EN
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Pvc Free:
Yes
Magnetic Hold Current:
750 A
Awg Gauge:
AWG 4...AWG 4/0 aluminium/copper terminal
Product Name:
PowerPact J
Ambient Air Temperature For Operation:
-2-70 °C
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Line Rated Current:
150-150 A
Height:
191 mm
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Net Weight:
2.4 kg
Ip Degree Of Protection:
front cover IP40
Product Or Component Type:
circuit breaker
Magnetic Tripping Current:
1750-1750 A
Mounting Support:
lug
Sustainable Offer Status:
Green Premium product
Pollution Degree:
3 IEC 60947-1
Poles Description:
2P
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Depth:
86 mm
Circuit Breaker Application:
HACR rated
Warranty:
18 months
Quality Labels:
CE
Rohs Exemption Information:
Yes
Communication Interface:
Modbus || Ethernet
Mercury Free:
Yes
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Utilisation Category:
category A
  • Schneider Electric JGL26150 Molded Case Circuit Breaker 600V 150A
  • Schneider Electric JGL26150 Molded Case Circuit Breaker 600V 150A
$4,818.00

Description

PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT J, 150A, 2 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose