- Range:
- PowerPact
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Rohs Exemption Information:
- Yes
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Environmental Disclosure:
- ENVPEP2206031EN
- Terminal Identifier:
- AL175JD
- Sustainable Offer Status:
- Green Premium product
- Awg Gauge:
- AWG 4...AWG 4/0 aluminium/copper terminal
- Magnetic Hold Current:
- 875 A
- Device Application:
- distribution
- Continuous Current Rating:
- 0.8
- Depth:
- 86 mm
- Quality Labels:
- CE
- Phase Connection:
- ABC
- Poles Description:
- 3P
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Magnetic Tripping Current:
- 1750-1750 A
- Product Or Component Type:
- circuit breaker
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Tightening Torque:
- 25-25 N.m 25-95 mm² (AWG 4...AWG 4/0)
- Mounting Support:
- lug
- Breaking Capacity Code:
- G
- Protection Type:
- overload protection || short-circuit protection
- Line Rated Current:
- 175-175 A
- Eu Rohs Directive:
- Compliant with Exemptions
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Mounting Mode:
- unit mount lug)
- Ip Degree Of Protection:
- front cover IP40
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Mounting Height:
- 4.5 in
- Height:
- 191 mm
- Suitability For Isolation:
- yes IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Ambient Air Temperature For Operation:
- -2-70 °C
- Net Weight:
- 2.4 kg
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Control Type:
- toggle
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Trip Unit Technology:
- thermal-magnetic
- Accessory / Separate Part Type:
- shunt trip 110...130 V AC compartment
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Communication Interface:
- Modbus || Ethernet
- Mercury Free:
- Yes
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Wire Stripping Length:
- 25 mm
- Utilisation Category:
- category A
- Product Name:
- PowerPact J
- Pollution Degree:
- 3 IEC 60947-1
- Pvc Free:
- Yes
- Warranty:
- 18 months
- Circuit Breaker Application:
- HACR rated
- Width:
- 104 mm
- Electrical Connection:
- lugs, line || lugs, load
- Network Frequency:
- 50/60 Hz
- Circularity Profile:
- ENVEOLI2206031EN
- Ambient Air Temperature For Storage:
- -50-85 °C
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating