Schneider Electric JGL36200AA Molded Case Circuit Breaker 600V 200A
Schneider Electric
$4,076.00
PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT J, 200A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. This unit includes a factory installed 1A/1B auxiliary switch. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Depth:
- 86 mm
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Rohs Exemption Information:
- Yes
- Line Rated Current:
- 200-200 A
- Pvc Free:
- Yes
- Mounting Height:
- 4.5 in
- Accessory / Separate Part Type:
- auxiliary switch 24 V AC/DC 1 NO + 1 NC cover frame
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Product Certifications:
- UL || CSA || NOM
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Phase Connection:
- ABC
- Net Weight:
- 2.4 kg
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Product Or Component Type:
- circuit breaker
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Ambient Air Temperature For Operation:
- -2-70 °C
- Sustainable Offer Status:
- Green Premium product
- Range:
- PowerPact
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Height:
- 191 mm
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Mounting Mode:
- unit mount lug)
- Communication Interface:
- Modbus || Ethernet
- Eu Rohs Directive:
- Compliant with Exemptions
- Product Name:
- PowerPact J
- Magnetic Tripping Current:
- 2000-2000 A
- Control Type:
- toggle
- Warranty:
- 18 months
- Width:
- 104 mm
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Electrical Connection:
- lugs, line || lugs, load
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Circularity Profile:
- ENVEOLI2206031EN
- Suitability For Isolation:
- yes IEC 60947-2
- Poles Description:
- 3P
- Utilisation Category:
- category A
- Magnetic Hold Current:
- 1000 A
- Trip Unit Technology:
- thermal-magnetic
- Ambient Air Temperature For Storage:
- -50-85 °C
- Protection Type:
- overload protection || short-circuit protection
- Device Application:
- distribution
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Breaking Capacity Code:
- G
- Mercury Free:
- Yes
- Continuous Current Rating:
- 0.8
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Wire Stripping Length:
- 25 mm
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Terminal Identifier:
- AL250JD
- Pollution Degree:
- 3 IEC 60947-1
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Environmental Disclosure:
- ENVPEP2206031EN
- Quality Labels:
- CE
- Mounting Support:
- lug
- Ip Degree Of Protection:
- front cover IP40
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View