- Product Or Component Type:
- circuit breaker
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Pvc Free:
- Yes
- Protection Type:
- overload protection || short-circuit protection
- Magnetic Tripping Current:
- 2000-2000 A
- Range:
- PowerPact
- Mounting Mode:
- unit mount lug)
- Device Application:
- distribution
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Width:
- 104 mm
- Warranty:
- 18 months
- Line Rated Current:
- 200-200 A
- Terminal Identifier:
- AL250JD
- Ambient Air Temperature For Operation:
- -2-70 °C
- Depth:
- 86 mm
- Eu Rohs Directive:
- Compliant with Exemptions
- Mounting Support:
- lug
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Rohs Exemption Information:
- Yes
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Trip Unit Technology:
- thermal-magnetic
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Mercury Free:
- Yes
- Environmental Disclosure:
- ENVPEP2206031EN
- Continuous Current Rating:
- 1
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Sustainable Offer Status:
- Green Premium product
- Breaking Capacity Code:
- G
- Circuit Breaker Application:
- HACR rated
- Communication Interface:
- Modbus || Ethernet
- Ip Degree Of Protection:
- front cover IP40
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Utilisation Category:
- category A
- Magnetic Hold Current:
- 1000 A
- Pollution Degree:
- 3 IEC 60947-1
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Height:
- 191 mm
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Electrical Connection:
- lugs, line || lugs, load
- Network Frequency:
- 50/60 Hz
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Poles Description:
- 3P
- Wire Stripping Length:
- 25 mm
- Quality Labels:
- CE
- Circularity Profile:
- ENVEOLI2206031EN
- Net Weight:
- 2.4 kg
- Ambient Air Temperature For Storage:
- -50-85 °C
- Product Name:
- PowerPact J
- Control Type:
- toggle
- Suitability For Isolation:
- yes IEC 60947-2