Schneider Electric JGL36200T Molded Case Circuit Breaker 600V 200A
Schneider Electric
$5,668.50
PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT J, 200A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. This unit allows field-interchangeable trip units. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Mounting Mode:
- unit mount lug)
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Continuous Current Rating:
- 0.8
- Product Or Component Type:
- circuit breaker
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Mounting Support:
- lug
- Mercury Free:
- Yes
- Network Frequency:
- 50/60 Hz
- Poles Description:
- 3P
- Utilisation Category:
- category A
- Ambient Air Temperature For Operation:
- -2-70 °C
- Range:
- PowerPact
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Net Weight:
- 2.4 kg
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Terminal Identifier:
- AL250JD
- Eu Rohs Directive:
- Compliant with Exemptions
- Depth:
- 86 mm
- Communication Interface:
- Modbus || Ethernet
- Protection Type:
- overload protection || short-circuit protection
- Product Certifications:
- UL || CSA || NOM
- Product Name:
- PowerPact J
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Device Application:
- distribution
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Rohs Exemption Information:
- Yes
- Line Rated Current:
- 200-200 A
- Circularity Profile:
- ENVEOLI2206031EN
- Sustainable Offer Status:
- Green Premium product
- Pvc Free:
- Yes
- Wire Stripping Length:
- 25 mm
- Electrical Connection:
- lugs, line || lugs, load
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Suitability For Isolation:
- yes IEC 60947-2
- Magnetic Hold Current:
- 1000 A
- Pollution Degree:
- 3 IEC 60947-1
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Trip Unit Technology:
- thermal-magnetic
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Circuit Breaker Application:
- HACR rated
- Breaking Capacity Code:
- G
- Width:
- 104 mm
- Warranty:
- 18 months
- Quality Labels:
- CE
- Control Type:
- toggle
- Magnetic Tripping Current:
- 2000-2000 A
- Environmental Disclosure:
- ENVPEP2206031EN
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Ambient Air Temperature For Storage:
- -50-85 °C
- Ip Degree Of Protection:
- front cover IP40
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Height:
- 191 mm