- Control Type:
- toggle
- Width:
- 104 mm
- Product Name:
- PowerPact J
- Ambient Air Temperature For Operation:
- -2-70 °C
- Utilisation Category:
- category A
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Communication Interface:
- Modbus || Ethernet
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Mounting Support:
- lug
- Ambient Air Temperature For Storage:
- -50-85 °C
- Depth:
- 86 mm
- Product Certifications:
- UL || CSA || NOM
- Mercury Free:
- Yes
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Wire Stripping Length:
- 25 mm
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2, LI
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Device Application:
- distribution
- Breaking Capacity Code:
- G
- Environmental Disclosure:
- ENVPEP2206032EN
- Line Rated Current:
- 250-250 A
- Net Weight:
- 2.4 kg
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Range:
- PowerPact
- Quality Labels:
- CE
- Ip Degree Of Protection:
- front cover IP40
- Continuous Current Rating:
- 1
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Warranty:
- 18 months
- Mounting Mode:
- unit mount lug)
- Eu Rohs Directive:
- Compliant with Exemptions
- Protection Type:
- overload protection || short-circuit protection
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile:
- ENVEOLI2206032EN
- Trip Unit Name:
- MicroLogic 3.2
- Rohs Exemption Information:
- Yes
- Poles Description:
- 3P
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm 1 LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Pollution Degree:
- 3 IEC 60947-1
- Height:
- 191 mm
- Terminal Identifier:
- AL250JD
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Pvc Free:
- Yes
- Suitability For Isolation:
- yes IEC 60947-2
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Sustainable Offer Status:
- Green Premium product
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Electrical Connection:
- lugs, line || lugs, load
- Network Frequency:
- 50/60 Hz