- Line Rated Current:
- 150-150 A
- Continuous Current Rating:
- 0.8
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Magnetic Hold Current:
- 750 A
- Pvc Free:
- Yes
- Accessory / Separate Part Type:
- shunt trip 110...130 V AC compartment
- Trip Unit Technology:
- thermal-magnetic
- Electrical Connection:
- lugs, line || lugs, load
- Breaking Capacity Code:
- J
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Sustainable Offer Status:
- Green Premium product
- Awg Gauge:
- AWG 4...AWG 4/0 aluminium/copper terminal
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Range:
- PowerPact
- Communication Interface:
- Modbus || Ethernet
- Circuit Breaker Application:
- HACR rated
- Quality Labels:
- CE
- Mounting Height:
- 4.5 in
- Pollution Degree:
- 3 IEC 60947-1
- Eu Rohs Directive:
- Compliant
- Depth:
- 86 mm
- Mounting Support:
- lug
- Product Or Component Type:
- circuit breaker
- Mercury Free:
- Yes
- Ambient Air Temperature For Storage:
- -50-85 °C
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Poles Description:
- 3P
- Protection Type:
- overload protection || short-circuit protection
- Network Frequency:
- 50/60 Hz
- Circularity Profile:
- ENVEOLI1311008
- Tightening Torque:
- 25-25 N.m 25-95 mm² (AWG 4...AWG 4/0)
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Ip Degree Of Protection:
- front cover IP40
- Magnetic Tripping Current:
- 1750-1750 A
- Product Name:
- PowerPact J
- Terminal Identifier:
- AL175JD
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Environmental Disclosure:
- ENVPEP1311008EN
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Mounting Mode:
- unit mount lug)
- Wire Stripping Length:
- 25 mm
- Ambient Air Temperature For Operation:
- -2-70 °C
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Suitability For Isolation:
- yes IEC 60947-2
- Warranty:
- 18 months
- Rohs Exemption Information:
- Yes
- Width:
- 104 mm
- Utilisation Category:
- category A
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Height:
- 191 mm
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Net Weight:
- 2.4 kg
- Product Certifications:
- UL || CSA || NOM
- Control Type:
- toggle
- Phase Connection:
- CA
- Device Application:
- distribution
- QN-QUOTE-REQUEST:
- true