Schneider Electric JJL36175T Molded Case Circuit Breaker 600V 175A
Schneider Electric
$5,432.00
PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 25kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT J, 175A, 3 pole, circuit breaker has a breaking capacity of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80%. This unit allows field-interchangeable trip units. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Terminal Identifier:
- AL175JD
- Mounting Support:
- lug
- Eu Rohs Directive:
- Compliant with Exemptions
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Utilisation Category:
- category A
- Phase Connection:
- ABC
- Mounting Mode:
- unit mount lug)
- Circularity Profile:
- ENVEOLI2206031EN
- Continuous Current Rating:
- 0.8
- Line Rated Current:
- 175-175 A
- Range:
- PowerPact
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Wire Stripping Length:
- 25 mm
- Communication Interface:
- Modbus || Ethernet
- Suitability For Isolation:
- yes IEC 60947-2
- Breaking Capacity Code:
- J
- Awg Gauge:
- AWG 4...AWG 4/0 aluminium/copper terminal
- Ambient Air Temperature For Operation:
- -2-70 °C
- Device Application:
- distribution
- Depth:
- 86 mm
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Quality Labels:
- CE
- Magnetic Tripping Current:
- 1750-1750 A
- Electrical Connection:
- lugs, line || lugs, load
- Ambient Air Temperature For Storage:
- -50-85 °C
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Warranty:
- 18 months
- Pollution Degree:
- 3 IEC 60947-1
- Mounting Height:
- 4.5 in
- Environmental Disclosure:
- ENVPEP2206031EN
- Magnetic Hold Current:
- 875 A
- Poles Description:
- 3P
- Protection Type:
- overload protection || short-circuit protection
- Trip Unit Technology:
- thermal-magnetic
- Pvc Free:
- Yes
- Ip Degree Of Protection:
- front cover IP40
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Net Weight:
- 2.4 kg
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Width:
- 104 mm
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Tightening Torque:
- 25-25 N.m 25-95 mm² (AWG 4...AWG 4/0)
- Mercury Free:
- Yes
- Control Type:
- toggle
- Product Certifications:
- UL || CSA || NOM
- Product Or Component Type:
- circuit breaker
- Product Name:
- PowerPact J
- Sustainable Offer Status:
- Green Premium product
- Height:
- 191 mm
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Network Frequency:
- 50/60 Hz
- Rohs Exemption Information:
- Yes
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating