- Terminal Identifier:
- AL175JD
                        
- Mounting Support:
- lug
                        
- Eu Rohs Directive:
- Compliant with Exemptions
                        
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
                        
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
                        
- Utilisation Category:
- category A
                        
- Phase Connection:
- ABC
                        
- Mounting Mode:
- unit mount lug)
                        
- Circularity Profile:
- ENVEOLI2206031EN
                        
- Continuous Current Rating:
- 0.8
                        
- Line Rated Current:
- 175-175 A
                        
- Range:
- PowerPact
                        
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
                        
- Wire Stripping Length:
- 25 mm
                        
- Communication Interface:
- Modbus || Ethernet
                        
- Suitability For Isolation:
- yes IEC 60947-2
                        
- Breaking Capacity Code:
- J
                        
- Awg Gauge:
- AWG 4...AWG 4/0 aluminium/copper terminal
                        
- Ambient Air Temperature For Operation:
- -2-70 °C
                        
- Device Application:
- distribution
                        
- Depth:
- 86 mm
                        
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
                        
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
                        
- Quality Labels:
- CE
                        
- Magnetic Tripping Current:
- 1750-1750 A
                        
- Electrical Connection:
- lugs, line || lugs, load
                        
- Ambient Air Temperature For Storage:
- -50-85 °C
                        
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
                        
- Warranty:
- 18 months
                        
- Pollution Degree:
- 3 IEC 60947-1
                        
- Mounting Height:
- 4.5 in
                        
- Environmental Disclosure:
- ENVPEP2206031EN
                        
- Magnetic Hold Current:
- 875 A
                        
- Poles Description:
- 3P
                        
- Protection Type:
- overload protection || short-circuit protection
                        
- Trip Unit Technology:
- thermal-magnetic
                        
- Pvc Free:
- Yes
                        
- Ip Degree Of Protection:
- front cover IP40
                        
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
                        
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
                        
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
                        
- Circuit Breaker Application:
- HACR rated
                        
- Net Weight:
- 2.4 kg
                        
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
                        
- Width:
- 104 mm
                        
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
                        
- Tightening Torque:
- 25-25 N.m 25-95 mm² (AWG 4...AWG 4/0)
                        
- Mercury Free:
- Yes
                        
- Control Type:
- toggle
                        
- Product Certifications:
- UL || CSA || NOM
                        
- Product Or Component Type:
- circuit breaker
                        
- Product Name:
- PowerPact J
                        
- Sustainable Offer Status:
- Green Premium product
                        
- Height:
- 191 mm
                        
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
                        
- Network Frequency:
- 50/60 Hz
                        
- Rohs Exemption Information:
- Yes
                        
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
                        
- QN-QUOTE-REQUEST:
- true