- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Utilisation Category:
- category A
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm 1 LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Net Weight:
- 2.4 kg
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Pvc Free:
- Yes
- Mounting Mode:
- unit mount lug)
- Suitability For Isolation:
- yes IEC 60947-2
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Control Type:
- toggle
- Circuit Breaker Application:
- HACR rated
- Continuous Current Rating:
- 1
- Terminal Identifier:
- AL250JD
- Product Or Component Type:
- circuit breaker
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Poles Description:
- 3P
- Line Rated Current:
- 250-250 A
- Environmental Disclosure:
- ENVPEP2206032EN
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Wire Stripping Length:
- 25 mm
- Pollution Degree:
- 3
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.2 A, LSIG
- Electrical Connection:
- lugs, line || lugs, load
- Width:
- 104 mm
- Eu Rohs Directive:
- Compliant with Exemptions
- Mounting Support:
- lug
- Ambient Air Temperature For Storage:
- -50-85 °C
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Depth:
- 86 mm
- Circularity Profile:
- ENVEOLI2206032EN
- Mercury Free:
- Yes
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Sustainable Offer Status:
- Green Premium product
- Breaking Capacity Code:
- J
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Warranty:
- 18 months
- Rohs Exemption Information:
- Yes
- Product Certifications:
- UL || CSA || NOM
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Quality Labels:
- CE
- Communication Interface:
- Modbus
- Height:
- 191 mm
- Protection Type:
- overload protection || short-circuit protection
- Ip Degree Of Protection:
- front cover IP40
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Ambient Air Temperature For Operation:
- -2-70 °C
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Network Frequency:
- 50/60 Hz
- Trip Unit Name:
- MicroLogic 6.2 A