- Trip Unit Technology:
- thermal-magnetic
- Continuous Current Rating:
- 0.8
- Wire Stripping Length:
- 25 mm
- Pollution Degree:
- 3
- Mounting Mode:
- unit mount lug)
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Protection Type:
- overload protection || short-circuit protection
- Circularity Profile:
- ENVEOLI2206031EN
- Product Certifications:
- UL || CSA || NOM
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Poles Description:
- 3P
- Network Frequency:
- 50/60 Hz
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- [Ith] Conventional Free Air Thermal Current:
- 117-217 A
- Terminal Identifier:
- AL250JD
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- Sustainable Offer Status:
- Green Premium product
- Electrical Connection:
- lugs, line || lugs, load
- Ambient Air Temperature For Storage:
- -50-85 °C
- Communication Interface:
- Modbus
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Height:
- 191 mm
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Mercury Free:
- Yes
- Width:
- 104 mm
- Warranty:
- 18 months
- Net Weight:
- 2.4 kg
- Breaking Capacity Code:
- J
- Mounting Support:
- lug
- Depth:
- 86 mm
- Ambient Air Temperature For Operation:
- -2-70 °C
- Quality Labels:
- CE
- Control Type:
- toggle
- Magnetic Hold Current:
- 1250 A
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Rohs Exemption Information:
- Yes
- Ip Degree Of Protection:
- front cover IP40
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Pvc Free:
- Yes
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Utilisation Category:
- category A
- Product Or Component Type:
- Motor Circuit Protector
- Environmental Disclosure:
- ENVPEP2206031EN
- Line Rated Current:
- 250-250 A
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Suitability For Isolation:
- yes IEC 60947-2
- Magnetic Tripping Current:
- 2500-2500 A