- Wire Stripping Length:
- 25 mm
- Protection Type:
- overload protection || short-circuit protection
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Depth:
- 86 mm
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Utilisation Category:
- category A
- Environmental Disclosure:
- ENVPEP2206031EN
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Sustainable Offer Status:
- Green Premium product
- Magnetic Hold Current:
- 875 A
- Poles Description:
- 3P
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Pollution Degree:
- 3
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Awg Gauge:
- AWG 4...AWG 4/0 aluminium/copper terminal
- Communication Interface:
- Modbus
- Suitability For Isolation:
- yes IEC 60947-2
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Height:
- 191 mm
- Phase Connection:
- ABC
- Ambient Air Temperature For Storage:
- -50-85 °C
- Net Weight:
- 2.4 kg
- Mounting Mode:
- I-Line bracket)
- Product Certifications:
- UL || CSA || NOM
- Electrical Connection:
- I-Line connection, line || lugs, load
- Continuous Current Rating:
- 0.8
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Ambient Air Temperature For Operation:
- -2-70 °C
- Tightening Torque:
- 25-25 N.m 25-95 mm² (AWG 4...AWG 4/0)
- Magnetic Tripping Current:
- 1750-1750 A
- Eu Rohs Directive:
- Compliant with Exemptions
- Circularity Profile:
- ENVEOLI2206031EN
- Mounting Support:
- bracket
- Quality Labels:
- CE
- Circuit Breaker Application:
- HACR rated
- Width:
- 104 mm
- Mercury Free:
- Yes
- Mounting Height:
- 4.5 in
- Warranty:
- 18 months
- Ip Degree Of Protection:
- front cover IP40
- Terminal Identifier:
- AL175JD
- Network Frequency:
- 50/60 Hz
- Line Rated Current:
- 175-175 A
- Breaking Capacity Code:
- L
- Trip Unit Technology:
- thermal-magnetic
- Rohs Exemption Information:
- Yes
- Control Type:
- toggle
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Pvc Free:
- Yes