- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Magnetic Hold Current:
- 1125 A
- Control Type:
- toggle
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Eu Rohs Directive:
- Compliant with Exemptions
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Environmental Disclosure:
- ENVPEP2206031EN
- Pollution Degree:
- 3
- Utilisation Category:
- category A
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Width:
- 104 mm
- Protection Type:
- overload protection || short-circuit protection
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Ambient Air Temperature For Operation:
- -2-70 °C
- Magnetic Tripping Current:
- 2250-2250 A
- Pvc Free:
- Yes
- Wire Stripping Length:
- 25 mm
- Circularity Profile:
- ENVEOLI2206031EN
- Product Or Component Type:
- circuit breaker
- Product Certifications:
- UL || CSA || NOM
- Electrical Connection:
- I-Line connection, line || lugs, load
- Mounting Mode:
- I-Line bracket)
- Height:
- 191 mm
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Warranty:
- 18 months
- Mounting Support:
- bracket
- Continuous Current Rating:
- 0.8
- Circuit Breaker Application:
- HACR rated
- Terminal Identifier:
- AL250JD
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Ip Degree Of Protection:
- front cover IP40
- Depth:
- 86 mm
- Suitability For Isolation:
- yes IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Communication Interface:
- Modbus
- Breaking Capacity Code:
- L
- Quality Labels:
- CE
- Ambient Air Temperature For Storage:
- -50-85 °C
- Poles Description:
- 3P
- Rohs Exemption Information:
- Yes
- Line Rated Current:
- 225-225 A
- Mercury Free:
- Yes
- Trip Unit Technology:
- thermal-magnetic
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Mounting Height:
- 4.5 in
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Sustainable Offer Status:
- Green Premium product
- Net Weight:
- 2.4 kg
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Phase Connection:
- ABC