- Trip Unit Technology:
- thermal-magnetic
- Pvc Free:
- Yes
- Magnetic Hold Current:
- 750 A
- Utilisation Category:
- category A
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Net Weight:
- 2.4 kg
- Network Frequency:
- 50/60 Hz
- Circuit Breaker Application:
- HACR rated
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Tightening Torque:
- 25-25 N.m 25-95 mm² (AWG 4...AWG 4/0)
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Sustainable Offer Status:
- Green Premium product
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Suitability For Isolation:
- yes IEC 60947-2
- Circularity Profile:
- ENVEOLI2206031EN
- Communication Interface:
- Modbus
- Continuous Current Rating:
- 0.8
- Electrical Connection:
- lugs, line || lugs, load
- Awg Gauge:
- AWG 4...AWG 4/0 aluminium/copper terminal
- Width:
- 104 mm
- Wire Stripping Length:
- 25 mm
- Mounting Mode:
- unit mount lug)
- Quality Labels:
- CE
- Terminal Identifier:
- AL175JD
- Mercury Free:
- Yes
- Control Type:
- toggle
- Product Certifications:
- UL || CSA || NOM
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Eu Rohs Directive:
- Compliant with Exemptions
- Environmental Disclosure:
- ENVPEP2206031EN
- Mounting Support:
- lug
- Pollution Degree:
- 3
- Rohs Exemption Information:
- Yes
- Product Or Component Type:
- circuit breaker
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Depth:
- 86 mm
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Poles Description:
- 3P
- Magnetic Tripping Current:
- 1750-1750 A
- Ambient Air Temperature For Operation:
- -2-70 °C
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Ambient Air Temperature For Storage:
- -50-85 °C
- Breaking Capacity Code:
- L
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Protection Type:
- overload protection || short-circuit protection
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Warranty:
- 18 months
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Height:
- 191 mm
- Line Rated Current:
- 150-150 A
- Ip Degree Of Protection:
- front cover IP40
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2