- Mounting Mode:
- unit mount lug)
- Trip Unit Technology:
- thermal-magnetic
- Magnetic Hold Current:
- 1000 A
- Communication Interface:
- Modbus
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Circularity Profile:
- ENVEOLI2206031EN
- Product Certifications:
- UL || CSA || NOM
- Depth:
- 86 mm
- Wire Stripping Length:
- 25 mm
- Protection Type:
- overload protection || short-circuit protection
- Sustainable Offer Status:
- Green Premium product
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Pvc Free:
- Yes
- Suitability For Isolation:
- yes IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Utilisation Category:
- category A
- Poles Description:
- 3P
- Control Type:
- toggle
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Electrical Connection:
- lugs, line || lugs, load
- Environmental Disclosure:
- ENVPEP2206031EN
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Ambient Air Temperature For Operation:
- -2-70 °C
- Network Frequency:
- 50/60 Hz
- Terminal Identifier:
- AL250JD
- Eu Rohs Directive:
- Compliant with Exemptions
- Mercury Free:
- Yes
- Product Or Component Type:
- circuit breaker
- Continuous Current Rating:
- 0.8
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Width:
- 104 mm
- Line Rated Current:
- 200-200 A
- Magnetic Tripping Current:
- 2000-2000 A
- Ambient Air Temperature For Storage:
- -50-85 °C
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Breaking Capacity Code:
- L
- Quality Labels:
- CE
- Mounting Support:
- lug
- Ip Degree Of Protection:
- front cover IP40
- Warranty:
- 18 months
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Height:
- 191 mm
- Rohs Exemption Information:
- Yes
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Pollution Degree:
- 3
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Net Weight:
- 2.4 kg