Schneider Electric JLL36250LV Molded Case Circuit Breaker 600V 250A
Schneider Electric
$13,569.00
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 50kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT J, 250A, 3 pole, circuit breaker has a breaking capacity of 50kA at 600VAC. This circuit breaker has a continuous current rating of 80%. This unit includes a control wire terminal on the load end. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Breaking Capacity Code:
- L
- Sustainable Offer Status:
- Green Premium product
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Net Weight:
- 2.4 kg
- Mounting Support:
- lug
- Communication Interface:
- Modbus
- Pollution Degree:
- 3
- Line Rated Current:
- 250-250 A
- Ambient Air Temperature For Operation:
- -2-70 °C
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Protection Type:
- overload protection || short-circuit protection
- Electrical Connection:
- lugs, line || lugs, load
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Eu Rohs Directive:
- Compliant with Exemptions
- Ip Degree Of Protection:
- front cover IP40
- Height:
- 191 mm
- Accessory / Separate Part Type:
- control wire OFF end
- Magnetic Hold Current:
- 1250 A
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Poles Description:
- 3P
- Utilisation Category:
- category A
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Environmental Disclosure:
- ENVPEP2206031EN
- Pvc Free:
- Yes
- Circularity Profile:
- ENVEOLI2206031EN
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Terminal Identifier:
- AL250JD
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Mercury Free:
- Yes
- Depth:
- 86 mm
- Suitability For Isolation:
- yes IEC 60947-2
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Product Or Component Type:
- circuit breaker
- Trip Unit Technology:
- thermal-magnetic
- Ambient Air Temperature For Storage:
- -50-85 °C
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Control Type:
- toggle
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Network Frequency:
- 50/60 Hz
- Quality Labels:
- CE
- Width:
- 104 mm
- Magnetic Tripping Current:
- 2500-2500 A
- Rohs Exemption Information:
- Yes
- Warranty:
- 18 months
- Mounting Mode:
- unit mount lug)
- Continuous Current Rating:
- 0.8
- Wire Stripping Length:
- 25 mm
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View