- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Ambient Air Temperature For Storage:
- -50-85 °C
- Ambient Air Temperature For Operation:
- -2-70 °C
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Mounting Mode:
- unit mount lug)
- Sustainable Offer Status:
- Green Premium product
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm 1 LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Network Frequency:
- 50/60 Hz
- Quality Labels:
- CE
- Width:
- 104 mm
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Control Type:
- toggle
- Trip Unit Name:
- MicroLogic 3.2
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Product Certifications:
- UL || CSA || NOM
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Protection Type:
- overload protection || short-circuit protection
- Circularity Profile:
- ENVEOLI2206032EN
- Rohs Exemption Information:
- Yes
- Continuous Current Rating:
- 0.8
- Circuit Breaker Application:
- HACR rated
- Pvc Free:
- Yes
- Breaking Capacity Code:
- L
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Terminal Identifier:
- AL250JD
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2, LI
- Ip Degree Of Protection:
- front cover IP40
- Net Weight:
- 2.4 kg
- Mounting Support:
- lug
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Mercury Free:
- Yes
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Depth:
- 86 mm
- Electrical Connection:
- lugs, line || lugs, load
- Poles Description:
- 3P
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Line Rated Current:
- 250-250 A
- Eu Rohs Directive:
- Compliant with Exemptions
- Communication Interface:
- Modbus
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Environmental Disclosure:
- ENVPEP2206032EN
- Pollution Degree:
- 3
- Height:
- 191 mm
- Wire Stripping Length:
- 25 mm
- Product Or Component Type:
- circuit breaker
- Suitability For Isolation:
- yes IEC 60947-2
- Warranty:
- 18 months
- Utilisation Category:
- category A
- QN-QUOTE-REQUEST:
- true