- Suitability For Isolation:
- yes IEC 60947-2
- Sustainable Offer Status:
- Green Premium product
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Mounting Mode:
- unit mount lug)
- Product Or Component Type:
- circuit breaker
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Protection Type:
- overload protection || short-circuit protection
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Magnetic Tripping Current:
- 2000-2000 A
- Breaking Capacity Code:
- L
- Mounting Support:
- lug
- Electrical Connection:
- terminal nut, line || lugs, load
- Warranty:
- 18 months
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Rohs Exemption Information:
- Yes
- Poles Description:
- 3P
- Mercury Free:
- Yes
- Product Certifications:
- UL || CSA || NOM
- Circularity Profile:
- ENVEOLI1311008
- Environmental Disclosure:
- ENVPEP1311008EN
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Control Type:
- toggle
- Line Rated Current:
- 200-200 A
- Communication Interface:
- Modbus
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Net Weight:
- 2.4 kg
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Network Frequency:
- 50/60 Hz
- Continuous Current Rating:
- 0.8
- Depth:
- 86 mm
- Wire Stripping Length:
- 25 mm
- Ambient Air Temperature For Storage:
- -50-85 °C
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Trip Unit Technology:
- thermal-magnetic
- Eu Rohs Directive:
- Compliant
- Terminal Identifier:
- AL250JD
- Width:
- 104 mm
- Magnetic Hold Current:
- 1000 A
- Height:
- 191 mm
- Quality Labels:
- CE
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Pollution Degree:
- 3
- Pvc Free:
- Yes
- Utilisation Category:
- category A
- Ambient Air Temperature For Operation:
- -2-70 °C
- Ip Degree Of Protection:
- front cover IP40