- Magnetic Hold Current:
- 1125 A
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Utilisation Category:
- category A
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Pvc Free:
- Yes
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Eu Rohs Directive:
- Compliant
- Trip Unit Technology:
- thermal-magnetic
- Electrical Connection:
- terminal nut, line || lugs, load
- Network Frequency:
- 50/60 Hz
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Ambient Air Temperature For Operation:
- -2-70 °C
- Sustainable Offer Status:
- Green Premium product
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Terminal Identifier:
- AL250JD
- Mounting Support:
- lug
- Width:
- 104 mm
- Warranty:
- 18 months
- Environmental Disclosure:
- ENVPEP1311008EN
- Pollution Degree:
- 3
- Ambient Air Temperature For Storage:
- -50-85 °C
- Communication Interface:
- Modbus
- Magnetic Tripping Current:
- 2250-2250 A
- Mercury Free:
- Yes
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Mounting Mode:
- unit mount lug)
- Circularity Profile:
- ENVEOLI1311008
- Quality Labels:
- CE
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Rohs Exemption Information:
- Yes
- Net Weight:
- 2.4 kg
- Circuit Breaker Application:
- HACR rated
- Control Type:
- toggle
- Breaking Capacity Code:
- L
- Product Or Component Type:
- circuit breaker
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Continuous Current Rating:
- 0.8
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Ip Degree Of Protection:
- front cover IP40
- Line Rated Current:
- 225-225 A
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Depth:
- 86 mm
- Wire Stripping Length:
- 25 mm
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Height:
- 191 mm
- Poles Description:
- 3P
- Protection Type:
- overload protection || short-circuit protection
- Suitability For Isolation:
- yes IEC 60947-2
- QN-QUOTE-REQUEST:
- true