- Device Application:
- distribution
- Width:
- 140 mm
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Eu Rohs Directive:
- Compliant with Exemptions
- Product Name:
- PowerPact L
- Product Or Component Type:
- circuit breaker
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Depth:
- 110 mm
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Ambient Air Temperature For Operation:
- -2-70 °C
- Sustainable Offer Status:
- Green Premium product
- Product Certifications:
- UL || CSA || NOM
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3 S, LSI
- Phase Connection:
- ABC
- Color:
- Black
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Suitability For Isolation:
- yes IEC 60947-2
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Awg Gauge:
- AWG 3/0...500 kcmil aluminium/copper
- Utilisation Category:
- category A
- Poles Description:
- 3P
- Terminal Identifier:
- AL600LF52K3
- Protection Technology:
- current limiter
- Range:
- PowerPact
- Warranty:
- 18 months
- Device Short Name:
- L-Frame
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Mounting Height:
- 6 in
- Trip Unit Name:
- MicroLogic 3.3 S
- Control Type:
- toggle
- Mercury Free:
- Yes
- Mounting Mode:
- I-Line bracket)
- Environmental Disclosure:
- ENVPEP2206029EN
- Wire Stripping Length:
- 31 mm
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Ambient Air Temperature For Storage:
- -50-85 °C
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 14 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Pollution Degree:
- 3 IEC 60947-1
- Circularity Profile:
- ENVEOLI2206029EN
- Mounting Support:
- bracket
- Electrical Connection:
- I-Line connection, line || lugs, load
- Circuit Breaker Application:
- HACR rated
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Net Weight:
- 6.2 kg
- Tightening Torque:
- 50-50 N.m 95-240 mm² (AWG 3/0...500 kcmil)
- Line Rated Current:
- 400-400 A
- Height:
- 340 mm
- Continuous Current Rating:
- 0.8
- Breaking Capacity Code:
- D
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Rohs Exemption Information:
- Yes
- Communication Interface:
- Modbus || Ethernet
- Ip Degree Of Protection:
- front cover IP40
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Pvc Free:
- Yes
- Network Frequency:
- 50/60 Hz
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2